Closed-Loop Actuator (CLA). A basic object with feedback, used with any form of actuator.
|
| |
Network Variables | Configuration Properties |
nviValue nvoValueFb
nviPreset nvoActPosnFb nvoPresetFb
| nciActFbDly nciAlarmClearT1 nciAlarmClearT2 nciAlarmSetT1 nciAlarmSetT2 nciDefault nciDriveT nciHighLim1 nciHighLim2 nciInFbDly nciLimHystHi1 nciLimHystHi2 nciLimHystLow1 nciLimHystLow2 nciLocation nciLowLim1 nciLowLim2 nciMaxReceiveT nciOffDly nciOutInhT nciOverBehave nciOverValue nciTransTblX nciTransTblY
|
| |
Details: |
| Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
| Index:
| 5 |
| Obsolete:
| no |
| Key:
| 4 |
|
Inheriting:
| no |
|
Principal Variable
| nviValue |
Mandatory Network Variables |
| nviValue | Value input.: Dictates the desired state of the actuator, determined by the specific application.
|
| Member Number:
| 1 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nvoValueFb | Value feedback output.: Transmits the current value of the input NV, used to synchronize source objects in multiple relationships.
|
| Member Number:
| 2 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
Optional Network Variables |
| nviPreset | Preset input.: Used to program or control the preset function.
|
| Member Number:
| 3 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nvoActPosnFb | Actual position feedback output.: Present position of the actuator, can be used as part of a control loop and for monitoring purposes.
|
| Member Number:
| 4 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
| nvoPresetFb | Preset feedback output.: Transmits the setting associated with the current recalled or programmed preset.
|
| Member Number:
| 5 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
Optional Configuration Properties |
| nciDefault | Default output.: The level the actuator should adopt in certain default conditions.
|
|
| nciDriveT | Drive time.: Time to be taken by the actuator to move from one extreme to the other.
|
|
| nciLocation | Location label.: Provides descriptive physical location information related to the object.
|
|
| nciMaxReceiveT | Maximum receive time.: Maximum time that elapses after the last update to the input NV before actuator adopts the default output.
|
| Member Number:
| 4 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciOffDly | Turn-off delay.: Used for SNVT_switch or SNVT_lev_disc to determine the length of time the load remains energized after a change from ON to OFF is received.
|
|
| nciInFbDly | Input value feedback delay.: The time period after the last update in a succession of changes to the input, before the feedback output is updated.
|
| Member Number:
| 6 | |
Base type:
| | |
Applies to
| nvoValueFb | | Array:
| not permitted |
|
| nciActFbDly | Actual position feedback delay.: The period for updating the feedback output when the actuator position does not match the requested position.
|
| Member Number:
| 7 | |
Base type:
| | |
Applies to
| nvoActPosnFb | | Array:
| not permitted |
|
| nciHighLim1 | High limit 1.: Used to remotely set the alarm high limit 1.
|
| Member Number:
| 8 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciHighLim2 | High limit 2.: Used to remotely set the alarm high limit 2.
|
| Member Number:
| 9 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciLowLim1 | Low limit 1.: Used to remotely set the alarm low limit 1.
|
| Member Number:
| 10 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciLowLim2 | Low limit 2.: Used to remotely set the alarm low limit 2.
|
| Member Number:
| 11 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciAlarmSetT1 | Alarm set time 1.: The time period that an alarm 1 condition must exist before it is regarded as a valid alarm.
|
| Member Number:
| 12 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciAlarmSetT2 | Alarm set time 2.: The time period that an alarm 2 condition must exist before it is regarded as a valid alarm.
|
| Member Number:
| 13 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciAlarmClearT1 | Alarm clear time 1.: The time period that an alarm 1 condition must not exist before it is regarded as a valid cleared alarm.
|
| Member Number:
| 14 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciAlarmClearT2 | Alarm clear time 2.: The time period that an alarm 2 condition must not exist before it is regarded as a valid cleared alarm.
|
| Member Number:
| 15 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciLimHystHi1 | Hysteresis high 1.: The hysteresis level for the value field of the alarm high 1 comparison threshold.
|
| Member Number:
| 16 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciLimHystHi2 | Hysteresis high 2.: The hysteresis level for the value field of the alarm high 2 comparison threshold.
|
| Member Number:
| 17 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciLimHystLow1 | Hysteresis low 1.: The hysteresis level for the value field of the alarm low 1 comparison threshold.
|
| Member Number:
| 18 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciLimHystLow2 | Hysteresis low 2.: The hysteresis level for the value field of the alarm low 2 comparison threshold.
|
| Member Number:
| 19 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciOutInhT | Alarm output inhibit time.: Time period for which alarms are inhibited after enabling, node reset, or node is put on line.
|
| Member Number:
| 20 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciOverBehave | Override behavior.: The behavior of an actuator when an override request is received.
|
|
| nciOverValue | Override value.: Sets the value an actuator should adopt when an object is overridden and behavior is OV_SPECIFIED.
|
| Member Number:
| 22 | |
Base type:
| | |
Applies to
| nviValue | | Array:
| not permitted |
|
| nciTransTblX | Translation table X.: Used in conjunction with Translation table Y to create a linearization table.
|
|
| nciTransTblY | Translation table Y.: Used in conjunction with Translation table X to create a linearization table.
|
|