Boiler Controller.. Can be used as an interface to a staged or a modulating boiler.
|
| |
Network Variables | Configuration Properties |
nviBoilerEnable nvoBoilerState nvoEffectSetpt
nviApplicMode nviBoilerCmd nviOutdoorTemp nviPumpSpeedCmd nviReturnTemp nviSetpoint nviSupplyTemp nvoBoilerLoad nvoBypassValve nvoLocalOATemp nvoLocalRetTemp nvoLocalSupTemp nvoOutdoorTemp nvoPumpSpeed nvoReturnTemp nvoSupplyTemp
| nciHeatSetpt nciSndHrtBt
nciLocation nciMinOutTm nciOffDelay nciPowerUp nciRcvHrtBt
|
| |
Details: |
| Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
| Index:
| 22 |
| Obsolete:
| no |
| Key:
| 8301 |
|
Inheriting:
| no |
Mandatory Network Variables |
| nviBoilerEnable | Boiler enable input.: Used to disable (stop) boiler operation, or to enable (automatic, local, or remote) boiler operation.
|
| Member Number:
| 1 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nvoBoilerState | Boiler state output.: Boiler's present level of heat output, as well as the requested firing rate of a remote boiler.
|
| Member Number:
| 2 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
| nvoEffectSetpt | Effective setpoint output.: Used to monitor the effective temperature setpoint.
|
| Member Number:
| 3 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged | | Minimum:
| 0,00 | | Maximum:
| 150,00 |
|
Optional Network Variables |
| nviApplicMode | Application mode input.: Used to coordinate the boiler controller node with any supervisory controller.
|
| Member Number:
| 4 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nviPumpSpeedCmd | Pump speed command input.: Used to connect an external pump control to the node or to allow an override of the pump speed.
|
| Member Number:
| 5 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nviSupplyTemp | Supply temperature input.: Used to connect an external supply temperature sensor to the node.
|
| Member Number:
| 6 | |
Base type:
| | | Direction:
| input | | Service:
| any | | Minimum:
| 0,00 | | Maximum:
| 150,00 |
|
| nviOutdoorTemp | Outside air temperature input.: Represents information from an outdoor air temperature sensor.
|
| Member Number:
| 7 | |
Base type:
| | | Direction:
| input | | Service:
| any | | Minimum:
| -40,00 | | Maximum:
| 50,00 |
|
| nviReturnTemp | Return temperature input.: Used to connect an external return temperature sensor to the node.
|
| Member Number:
| 8 | |
Base type:
| | | Direction:
| input | | Service:
| any | | Minimum:
| 0,00 | | Maximum:
| 150,00 |
|
| nviSetpoint | Temperature setpoint input (absolute): Used to allow the heating setpoint for the boiler water temperature to be changed via the network.
|
| Member Number:
| 9 | |
Base type:
| | | Direction:
| input | | Service:
| any | | Minimum:
| 0,00 | | Maximum:
| 150,00 |
|
| nviBoilerCmd | Boiler command input.: Used to command the boiler state and firing rate of the boiler controller (e.g., to disable the boiler, or allow automatic control)
|
| Member Number:
| 10 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nvoBoilerLoad | Boiler load output.: Present heat/cool energy demand of the unit. Negative values indicate that heating energy is required (or in use) by the boiler controller.
|
| Member Number:
| 11 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged | | Maximum:
| 0,000 |
|
| nvoSupplyTemp | Supply temperature output.: Used to monitor the supply water temperature that the boiler controller is using for control.
|
| Member Number:
| 12 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged | | Minimum:
| 0,00 | | Maximum:
| 150,00 |
|
| nvoLocalSupTemp | Local supply temperature output.: Present value of a locally wired supply water temperature sensor.
|
| Member Number:
| 13 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged | | Minimum:
| -40,00 | | Maximum:
| 70,00 |
|
| nvoReturnTemp | Return temperature output.: Used to monitor the return water temperature that the boiler controller is using for control.
|
| Member Number:
| 14 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged | | Minimum:
| 0,00 | | Maximum:
| 150,00 |
|
| nvoLocalRetTemp | Local return temperature output.: Present value of a locally wired return water temperature sensor.
|
| Member Number:
| 15 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged | | Minimum:
| -40,00 | | Maximum:
| 70,00 |
|
| nvoPumpSpeed | Pump speed output.: Actual pump speed of a local multi-speed pump, as well as the requested speed of a remote pump.
|
| Member Number:
| 16 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
| nvoBypassValve | Bypass valve output.: Present value of the bypass control valve position (if hardwired) or can be used to control a remote bypass valve.
|
| Member Number:
| 17 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged | | Minimum:
| 0,000 | | Maximum:
| 100,000 |
|
| nvoOutdoorTemp | Outdoor air temperature output.: Used to monitor the outdoor air temperature that the boiler controller is using for control.
|
| Member Number:
| 18 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged | | Minimum:
| -40,00 | | Maximum:
| 70,00 |
|
| nvoLocalOATemp | Local outdoor air temperature output.: Present value of a locally wired outdoor air temperature sensor.
|
| Member Number:
| 19 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged | | Minimum:
| -40,00 | | Maximum:
| 70,00 |
|
Mandatory Configuration Properties |
| nciSndHrtBt | Send heartbeat.: Maximum period of time that expires before the specified network variable outputs will automatically be updated.
|
|
| nciHeatSetpt | Heating setpoint.: This applies to the setpoint NV input if one exists; otherwise, it applies to the hardwired input.
|
| Member Number:
| 4 | |
Base type:
| | |
Applies to
| SFPTboilerController | | Array:
| not permitted | | Minimum:
| 0,00 | | Maximum:
| 150,00 | | Default:
| 35,00 |
|
Optional Configuration Properties |
| nciPowerUp | Power-up enable.: Default power-up and restart modes of the boiler controller.
|
|
| nciRcvHrtBt | Receive heartbeat.: Maximum time that elapses after the last update to a specified network variable input before the boiler controller starts to use its default values.
|
|
| nciLocation | Location label.: Provides descriptive physical location information related to the object.
|
|
| nciMinOutTm | Minimum send time.: Minimum period of time between automatic network variable output transmissions.
|
|
| nciOffDelay | Turn-off delay time.: Used to control the time delay that the pump remains "on" after a new command to turn the pump "off" is issued.
|
|