SCPTmaxFlowHeat

Overview:

Maximum heating airflow..  The maximum airflow setpoint of a VAV terminal while heating. 

This configuration property sets the maximum airflow setpoint of a device such as a VAV terminal while heating. The value of the heating maximum-flow setpoint must be validated against the value of the heating minimum-flow setpoint as follows:

0<= heating minimum flow setpoint <=heating maximum flow setpoint


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 37
Obsolete: no
Size: 2
Programmatic Name: SCPTmaxFlowHeat
Default: 65535
Neuron C Type:
SNVT_flow
Formats:

SCPTmaxFlowHeat#SI:  text("%d")

SCPTmaxFlowHeat#US:  text("%d", *0.26418+0(0:837))

SCPTmaxFlowHeat#US_cfm:  text("%d", *2.1189+0(0:966))

Used by: