Variable-Speed Motor Drive.. Variable-Speed/Frequency Drive for Motors.
|
|
Network Variables | Configuration Properties |
nviDrvSpeedStpt nvoDrvSpeed
nviDrvSpeedScale nvoDrvCurnt nvoDrvPwr nvoDrvRunHours nvoDrvVolt
| nciMaxSpeed nciMinSpeed nciNmlFreq nciNmlSpeed nciRampDownTm nciRampUpTm nciSndHrtBt
nciDrvSpeedScale nciLocation nciMinOutTm nciRcvHrtBt
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 13 |
Obsolete:
| no |
Key:
| 6010 |
Inheriting:
| no |
Principal Variable
| nviDrvSpeedStpt |
Mandatory Network Variables |
nviDrvSpeedStpt | Drive speed setpoint.: Provides start/stop control and a low-resolution speed setpoint.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoDrvSpeed | Drive speed output.: Drive speed as a percentage of nominal speed.
|
Member Number:
| 4 |
Base type:
| | Direction:
| output | Service:
| any |
|
Optional Network Variables |
nviDrvSpeedScale | Drive speed setpoint scaling.: Negative values indicate a motor direction in reverse.
|
Member Number:
| 2 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoDrvCurnt | Drive current output.: Drive current (Amperes) output.
|
Member Number:
| 3 |
Base type:
| | Direction:
| output | Service:
| any | Minimum:
| 0,0 |
|
nvoDrvVolt | Drive voltage output.: The typical range is 0 to 700 volts.
|
Member Number:
| 5 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoDrvPwr | Drive power output.: Drive power (kW) output.
|
Member Number:
| 6 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoDrvRunHours | Drive total running hours.: The number of hours the drive has been actively running.
|
Member Number:
| 7 |
Base type:
| | Direction:
| output | Service:
| any |
|
Mandatory Configuration Properties |
nciMaxSpeed | Maximum motor speed.: The value is entered as a percent of nominal speed in RPM, as defined by the nominal speed configuration value.
|
|
nciMinSpeed | Minimum motor speed.: The value is entered as a percent of nominal speed in RPM, as defined by the nominal speed configuration value.
|
|
nciSndHrtBt | Maximum send time.: Controls the maximum period of time before the output values are transmitted.
|
|
nciNmlSpeed | Nominal motor speed in RPM.: This value is necessary to determine the minimum and maximum speed for the motor.
|
|
nciNmlFreq | Nominal motor frequency.: Typical default values include 50Hz and 60Hz.
|
|
nciRampUpTm | Minimum ramp-up time.: Minimum time of acceleration.
|
|
nciRampDownTm | Minimum ramp-down time.: Minimum time of deceleration.
|
|
Optional Configuration Properties |
nciRcvHrtBt | Maximum receive time.: Maximum time that elapses after the last update to the input NV before actuator adopts the default output.
|
|
nciMinOutTm | Minimum send time.: Controls the minimum period of time between output value transmissions.
|
|
nciLocation | Location label.: Provides descriptive physical location information related to the object.
|
|
nciDrvSpeedScale | Drive speed scaling default value.: Default value for drive speed setpoint scaling.
|
|