SCPTminFlowHeat

Overview:

Minimum heating airflow..  The minimum airflow setpoint of a VAV terminal while heating. 

This configuration property sets the minimum flow a VAV controller will control to when reheat is utilized.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 55
Obsolete: no
Size: 2
Programmatic Name: SCPTminFlowHeat
Default: 0
Neuron C Type:
SNVT_flow
Formats:

SCPTminFlowHeat#SI:  text("%d")

SCPTminFlowHeat#US:  text("%d", *0.26418+0(0:837))

SCPTminFlowHeat#US_cfm:  text("%d", *2.1189+0(0:966))

Used by:

SFPTsccAHU  SFPTsccChilledCeiling  SFPTsccFanCoil  SFPTsccHeatPump  SFPTsccRadiator  SFPTsccRooftop  SFPTsccSelfContained  SFPTsccUnitVentilator  SFPTsccVAV  SFPTspaceComfortController  SFPTvariableAirVolume