Air temperature sensor..
A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure.
The Web Link is: VDI - Room control functions (RA functions)
|
|
Network Variables | Configuration Properties |
nvoSensAirTemp
| cpMaxSendTime cpMinDeltaTemp cpMinSendTime
cpTmpOffset
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 111 |
Obsolete:
| no |
Key:
| 16104 |
Inheriting:
| no |
Mandatory Network Variables |
nvoSensAirTemp | Air temperature.:
|
Member Number:
| 1 |
Base type:
| | Direction:
| output | Service:
| any |
|
Mandatory Configuration Properties |
cpMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 2 |
Base type:
| |
Applies to
| nvoSensAirTemp | Array:
| not permitted | Default:
| 0,0 |
|
cpMinDeltaTemp | Minimum delta temperature.: The minimum change in temperature required to be treated as significant.
|
Member Number:
| 3 |
Base type:
| |
Applies to
| nvoSensAirTemp | Array:
| not permitted | Minimum:
| 0,00 | Default:
| 0,00 |
|
cpMinSendTime | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
Member Number:
| 4 |
Base type:
| |
Applies to
| nvoSensAirTemp | Array:
| not permitted | Default:
| 0,0 |
|
Optional Configuration Properties |
cpTmpOffset | Temperature offset.: Temperature offset for calibration.
|
|