Automatic Transfer Switch..
An ATS is a piece of electrical equipment that is used to monitor and automatically connect the best of two power sources to an electrical load. Normally at least one of the two power sources is a generator set that is directed by the ATS to start when the primary power source has failed.
|
|
Network Variables | Configuration Properties |
nviTestCmd nvoSrc1Available nvoSrc1Connected nvoSrc2Available nvoSrc2Connected nvoSrc2StartCmd
nviFaultResetCmd nviLoadShedCmd nviOverrideCmd nviRetransInhCmd nviTransInhCmd nvoFaultStatus nvoLoadCurrent nvoLoadPF nvoLoadRealPower nvoSrc1Frequency nvoSrc1StartCmd nvoSrc1VoltageLL nvoSrc1VoltageLN nvoSrc2Frequency nvoSrc2VoltageLL nvoSrc2VoltageLN
| nciLocation nciMaxSendTime nciMaxSendTimeNV14 nciMaxSendTimeNV15 nciMaxSendTimeNV16 nciMaxSendTimeNV17 nciMaxSendTimeNV18 nciMaxSendTimeNV19 nciMaxSendTimeNV20 nciMaxSendTimeNV21 nciMaxSendTimeNV22
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 55 |
Obsolete:
| no |
Key:
| 13120 |
Inheriting:
| no |
Mandatory Network Variables |
nviTestCmd | Test Command Input.: Allows an external node to test the ATS operation.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoSrc2StartCmd | Start Source 2 Command Output.: Allows the ATS to start and stop the alternate or emergency power source.
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoSrc1Available | Source 1 Available Output.: Indicates the availability of the normal power source (GenSet/Source 1)
|
Member Number:
| 3 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoSrc2Available | Source 2 Available Output.: Indicates the availability of the emergency power source (GenSet/Source 2)
|
Member Number:
| 4 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoSrc1Connected | Source 1 Connected Output.: Indicates the switch position of the ATS.
|
Member Number:
| 5 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoSrc2Connected | Source 2 Connected Output.: Indicates the switch position of the ATS.
|
Member Number:
| 6 |
Base type:
| | Direction:
| output | Service:
| any |
|
Optional Network Variables |
nviFaultResetCmd | Fault Reset Command Input.: Resets or attempts to clear an ATS fault.
|
Member Number:
| 7 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviLoadShedCmd | Load Shed Command Input.: Sheds the electrical load of the ATS.
|
Member Number:
| 8 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviTransInhCmd | Transfer Inhibit Command Input.: Inhibits the ATS from automatically transferring the load to the emergency power source (Source 2), when Source 2 becomes available.
|
Member Number:
| 9 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviRetransInhCmd | Retransfer Inhibit Command Input.: Inhibits the ATS from automatically transferring the load back to the normal power source (Source 1), when Source 1 becomes available.
|
Member Number:
| 10 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviOverrideCmd | Override Command Input.: Overrides a transfer or retransfer time delay, or transfer or retransfer inhibit.
|
Member Number:
| 11 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoSrc1StartCmd | Start Source 1 Command Output.: Allows the ATS to start and stop the Source 1.
|
Member Number:
| 12 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoFaultStatus | Fault Status Output.: Reports the presence of an ATS fault.
|
Member Number:
| 13 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoSrc1Frequency | Source 1 Frequency Output.: Line frequency of Source 1.
|
Member Number:
| 14 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoSrc2Frequency | Source 2 Frequency Output.: Line frequency of Source 2.
|
Member Number:
| 15 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoSrc1VoltageLL | Source 1 Line-to-Line Voltage Output.: Line-to-line voltage(s) of Source 1.
|
Member Number:
| 16 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoSrc2VoltageLL | Source 2 Line-to-Line Voltage Output.: Line-to-line voltage(s) of Source 2.
|
Member Number:
| 17 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoSrc1VoltageLN | Source 1 Line-to-Neutral Voltage Output.: Line-to-neutral voltage(s) of Source 1.
|
Member Number:
| 18 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoSrc2VoltageLN | Source 2 Line-to-Neutral Voltage Output.: Line-to-neutral voltage(s) of Source 2.
|
Member Number:
| 19 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoLoadCurrent | Load Current Output.: Line current(s) of the electrical load.
|
Member Number:
| 20 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoLoadPF | Load Power Factor Output.: Power factor of the electrical load.
|
Member Number:
| 21 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoLoadRealPower | Load Real Power Output.: Real power of the electrical load as a floating type ( in Watts)
|
Member Number:
| 22 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
Optional Configuration Properties |
nciLocation | Location: Provides descriptive physical location information related to the object.
|
|
nciMaxSendTimeNV14 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 2 |
Base type:
| |
Applies to
| nvoSrc1Frequency | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV15 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 3 |
Base type:
| |
Applies to
| nvoSrc2Frequency | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV16 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 4 |
Base type:
| |
Applies to
| nvoSrc1VoltageLL | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV17 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 5 |
Base type:
| |
Applies to
| nvoSrc2VoltageLL | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV18 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 6 |
Base type:
| |
Applies to
| nvoSrc1VoltageLN | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV19 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 7 |
Base type:
| |
Applies to
| nvoSrc2VoltageLN | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV20 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 8 |
Base type:
| |
Applies to
| nvoLoadCurrent | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV21 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 9 |
Base type:
| |
Applies to
| nvoLoadPF | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV22 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 10 |
Base type:
| |
Applies to
| nvoLoadRealPower | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTime | Maximum send time to be used across NVs 14-22.: The maximum period of time between consecutive transmissions of the current value.
|
|