Constant Light Controller.. The controller input is the ambient light level, and the output is the state and illumination level to the lamp actuator.
|
| |
Network Variables | Configuration Properties |
nviLuxLevel nviSetting nvoLampValue
nviManOverride
| nciLuxSetpoint
nciClOffDelay nciClOnDelay nciLocation nciMaxSendT nciMinSendT nciOnOffHyster nciPowerupSt nciSendOnDelta nciStep
|
| |
Details: |
| Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
| Index:
| 18 |
| Obsolete:
| no |
| Key:
| 3050 |
|
Inheriting:
| no |
|
Principal Variable
| nviLuxLevel |
Mandatory Network Variables |
| nviLuxLevel | Illumination level input value.: Ambient light level.
|
| Member Number:
| 1 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nviSetting | Setting input.: Selects the operating mode, and adjusts the setpoint of the constant light controller.
|
| Member Number:
| 2 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nvoLampValue | Lamp value output.: State for the lamp actuator (ON or OFF), and the percentage level of intensity.
|
| Member Number:
| 3 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
Optional Network Variables |
| nviManOverride | Manual override input.: Provides enable of manual control for the lamp value output.
|
| Member Number:
| 4 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
Mandatory Configuration Properties |
| nciLuxSetpoint | Illumination level setpoint.: Used to change the illumination level setpoint for the controller.
|
|
Optional Configuration Properties |
| nciLocation | Location label.: Provides descriptive physical location information related to the object.
|
|
| nciMinSendT | Minimum send time.: Minimum period between output NV transmissions (maximum transmission rate)
|
|
| nciMaxSendT | Send heartbeat.: Maximum period of time that expires before the object automatically transmits the present value of the lux level output NV.
|
|
| nciStep | Step: Used to determine the maximum step that the constant light controller is allowed to take to approach the target illumination level.
|
|
| nciSendOnDelta | Minimum change.: Amount by which the lamp value output must change before the lamp value is transmitted.
|
|
| nciOnOffHyster | ON/OFF hysteresis.: Hysteresis for the illumination level setpoint. The hysteresis is used in AUTO mode to switch-off and -on the lamp.
|
|
| nciClOffDelay | Light off delay.: Used to determine the delay after which the lamp value output is switched-off.
|
|
| nciClOnDelay | Light on delay.: Used to determine the delay after which the lamp value output is switched-on.
|
|
| nciPowerupSt | Power-up state.: Used to determine the state (mode) of the constant light controller object after power-up or reset. The state ("function") can be either SET_ON or SET_OFF.
|
| Member Number:
| 10 | |
Base type:
| | |
Applies to
| SFPTconstantLightController | | Array:
| not permitted | | Minimum:
| SET_OFF 0,0 -359,98 | | Maximum:
| SET_ON 100,0 360,00 | | Default:
| SET_OFF 0,0 0,00 |
|