Constant Light Controller.. The controller input is the ambient light level, and the output is the state and illumination level to the lamp actuator.
|
|
Network Variables | Configuration Properties |
nviLuxLevel nviSetting nvoLampValue
nviManOverride
| nciLuxSetpoint
nciClOffDelay nciClOnDelay nciLocation nciMaxSendT nciMinSendT nciOnOffHyster nciPowerupSt nciSendOnDelta nciStep
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 18 |
Obsolete:
| no |
Key:
| 3050 |
Inheriting:
| no |
Principal Variable
| nviLuxLevel |
Mandatory Network Variables |
nviLuxLevel | Illumination level input value.: Ambient light level.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviSetting | Setting input.: Selects the operating mode, and adjusts the setpoint of the constant light controller.
|
Member Number:
| 2 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoLampValue | Lamp value output.: State for the lamp actuator (ON or OFF), and the percentage level of intensity.
|
Member Number:
| 3 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
Optional Network Variables |
nviManOverride | Manual override input.: Provides enable of manual control for the lamp value output.
|
Member Number:
| 4 |
Base type:
| | Direction:
| input | Service:
| any |
|
Mandatory Configuration Properties |
nciLuxSetpoint | Illumination level setpoint.: Used to change the illumination level setpoint for the controller.
|
|
Optional Configuration Properties |
nciLocation | Location label.: Provides descriptive physical location information related to the object.
|
|
nciMinSendT | Minimum send time.: Minimum period between output NV transmissions (maximum transmission rate)
|
|
nciMaxSendT | Send heartbeat.: Maximum period of time that expires before the object automatically transmits the present value of the lux level output NV.
|
|
nciStep | Step: Used to determine the maximum step that the constant light controller is allowed to take to approach the target illumination level.
|
|
nciSendOnDelta | Minimum change.: Amount by which the lamp value output must change before the lamp value is transmitted.
|
|
nciOnOffHyster | ON/OFF hysteresis.: Hysteresis for the illumination level setpoint. The hysteresis is used in AUTO mode to switch-off and -on the lamp.
|
|
nciClOffDelay | Light off delay.: Used to determine the delay after which the lamp value output is switched-off.
|
|
nciClOnDelay | Light on delay.: Used to determine the delay after which the lamp value output is switched-on.
|
|
nciPowerupSt | Power-up state.: Used to determine the state (mode) of the constant light controller object after power-up or reset. The state ("function") can be either SET_ON or SET_OFF.
|
Member Number:
| 10 |
Base type:
| |
Applies to
| SFPTconstantLightController | Array:
| not permitted | Minimum:
| SET_OFF 0,0 -359,98 | Maximum:
| SET_ON 100,0 360,00 | Default:
| SET_OFF 0,0 0,00 |
|