Generator Set.. Used to control a generator set (genset) for power generation in primary or secondary systems.
|
|
Network Variables | Configuration Properties |
nviFaultResetCmd nviStartCmd nvoFaultStatus nvoRunStatus
nviShutdownCmd nvoBattery nvoCurrent nvoEngineRunTime nvoEngineSpeed nvoEngineStarts nvoEngineTemp nvoFrequency nvoGenEnergy nvoNFPA110Annun nvoOilPressure nvoPowerFactor nvoRealPower nvoVoltageLL nvoVoltageLN
| nciMaxSendTime
nciLocation nciMaxSendTimeNV03 nciMaxSendTimeNV13 nciMaxSendTimeNV14 nciMaxSendTimeNV15 nciMaxSendTimeNV16 nciMaxSendTimeNV17 nciMaxSendTimeNV19
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 56 |
Obsolete:
| no |
Key:
| 13110 |
Inheriting:
| no |
Mandatory Network Variables |
nviStartCmd | Start Command Input.: start and stop the generator set.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviFaultResetCmd | Fault Reset Command Input.: reset or clear a generator set fault.
|
Member Number:
| 2 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoRunStatus | Run Status Output.: running at rated speed and voltage and is ready to accept load.
|
Member Number:
| 3 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoFaultStatus | Fault Status Output.: report the presence of a generator set fault.
|
Member Number:
| 4 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
Optional Network Variables |
nviShutdownCmd | Shutdown Command Input.: emergency, unconditional shutdown/disable of run.
|
Member Number:
| 5 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoNFPA110Annun | NFPA 110 Annunciation Output.: report state of National Fire Protection Agency (USA) genset faults (NFPA s.110)
|
Member Number:
| 6 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoFrequency | Frequency Output.: output frequency of the generator set.
|
Member Number:
| 7 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoVoltageLL | Line-to-Line Voltage Output.: line-to-line output voltage(s) of the generator set.
|
Member Number:
| 8 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoVoltageLN | Line-to-Neutral Voltage Output.: line-to-neutral output voltage(s) of the generator set.
|
Member Number:
| 9 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoCurrent | Line Current Output.: output line current(s) of the generator set.
|
Member Number:
| 10 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoPowerFactor | Power Factor Output.: power factor of the generator set.
|
Member Number:
| 11 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoRealPower | Real Power Output.: real power output as a floating type ( in Watts)
|
Member Number:
| 12 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoGenEnergy | Generated Energy Output.: total (cumulative) electrical energy (WHR) generated by genset.
|
Member Number:
| 13 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoEngineSpeed | Engine Speed Output.: engine speed of the generator set.
|
Member Number:
| 14 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoEngineTemp | Engine Temperature Output.: engine temperature of the generator set.
|
Member Number:
| 15 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoOilPressure | Engine Oil Pressure Output.: engine oil pressure of the generator set.
|
Member Number:
| 16 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoBattery | Battery Voltage Output.: starting battery voltage of the engine.
|
Member Number:
| 17 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoEngineStarts | Engine Starts Output.: total number of successful engine starts.
|
Member Number:
| 18 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoEngineRunTime | Engine Run Time Output.: total (cumulative) run time of the engine.
|
Member Number:
| 19 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
Mandatory Configuration Properties |
nciMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 2 |
Base type:
| |
Applies to
| SFPTgeneratorSet | Array:
| not permitted | Default:
| 0,0 |
|
Optional Configuration Properties |
nciLocation | Location: Provides descriptive physical location information related to the object.
|
Member Number:
| 1 |
Base type:
| |
Applies to
| SFPTgeneratorSet | Array:
| not permitted | Default:
| 00*31 |
|
nciMaxSendTimeNV03 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 3 |
Base type:
| |
Applies to
| nvoRunStatus | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV13 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 4 |
Base type:
| |
Applies to
| nvoGenEnergy | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV14 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 5 |
Base type:
| |
Applies to
| nvoEngineSpeed | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV15 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 6 |
Base type:
| |
Applies to
| nvoEngineTemp | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV16 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 7 |
Base type:
| |
Applies to
| nvoOilPressure | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV17 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 8 |
Base type:
| |
Applies to
| nvoBattery | Array:
| not permitted | Default:
| 0,0 |
|
nciMaxSendTimeNV19 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 9 |
Base type:
| |
Applies to
| nvoEngineRunTime | Array:
| not permitted | Default:
| 0,0 |
|