Hardwired Full Ventilation.. The hardwired Full Ventilation profile is used to monitor a Hardwired Full Ventilation input.
|
|
Network Variables | Configuration Properties |
nviHwFullVent nvoHwFullVentFb
| cpAlarmTriggerState cpMaxSendTime cpReceiveHrtbt
nciLocation
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 106 |
Obsolete:
| no |
Key:
| 4313 |
Inheriting:
| no |
Mandatory Network Variables |
nviHwFullVent | Full Ventilation Input.: This input network variable is used to put the system on full ventilation.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoHwFullVentFb | Full Ventilation Output.: This output network variable is used to indicate that a system is on full ventilation.
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
Mandatory Configuration Properties |
cpMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 1 |
Base type:
| |
Applies to
| nvoHwFullVentFb | Array:
| not permitted | Default:
| 30,0 |
|
cpReceiveHrtbt | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 2 |
Base type:
| |
Applies to
| nviHwFullVent | Array:
| not permitted | Default:
| 30,0 |
|
cpAlarmTriggerState | Alarm Trigger state.:
This input configuration indicates the default state of the input signal. With this configuration property you could set if the alarm signal will be defected while ACTIVE HIGH or ACTIVE LOW.
|
|
Optional Configuration Properties |
nciLocation | Location: Provides descriptive physical location information related to the object.
|
|