SFPThardwiredFullVentilation

Hardwired Full Ventilation..  The hardwired Full Ventilation profile is used to monitor a Hardwired Full Ventilation input. 
 

Network Variables

Configuration Properties

nviHwFullVent
nvoHwFullVentFb

cpAlarmTriggerState
cpMaxSendTime
cpReceiveHrtbt

nciLocation

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 106
Obsolete: no
Key: 4313
Inheriting: no


Mandatory Network Variables

nviHwFullVentFull Ventilation Input.:   This input network variable is used to put the system on full ventilation. 
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nvoHwFullVentFbFull Ventilation Output.:   This output network variable is used to indicate that a system is on full ventilation. 
Member Number: 2
Base type:
SNVT_switch
Direction: output
Service: acknowledged


Mandatory Configuration Properties

cpMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 1
Base type:
SCPTmaxSendTime
Applies to nvoHwFullVentFb
Array: not permitted
Default: 30,0
cpReceiveHrtbtMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 2
Base type:
SCPTmaxRcvTime
Applies to nviHwFullVent
Array: not permitted
Default: 30,0
cpAlarmTriggerStateAlarm Trigger state.:   This input configuration indicates the default state of the input signal. With this configuration property you could set if the alarm signal will be defected while ACTIVE HIGH or ACTIVE LOW.  
Member Number: 3
Base type:
SCPTdefltBehave
Applies to SFPThardwiredFullVentilation
Array: not permitted
Default: 100,0 1


Optional Configuration Properties

nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 4
Base type:
SCPTlocation
Applies to SFPThardwiredFullVentilation
Array: not permitted
Default: 00*31