Hardwired Gas Detection Shutdown.. The hardwired Gas Detection Shutdown profile is used to monitor a Hardwired Gas Detection Alarm input which shuts down the HVAC system.
|
|
Network Variables | Configuration Properties |
nviHwGasDetection nvoHwGasDetectionFb
| cpAlarmTriggerState cpMaxSendTime cpReceiveHrtbt
nciLocation
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 104 |
Obsolete:
| no |
Key:
| 4310 |
Inheriting:
| no |
Mandatory Network Variables |
nviHwGasDetection | Gas Detection Shutdown Input.: This input network variable is used to initiate a Gas Detection shut down.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoHwGasDetectionFb | Gas Detection Shutdown Feedback.: This output network variable is used to indicate that a Gas Detection shutdown has occurred.
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
Mandatory Configuration Properties |
cpMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
|
cpReceiveHrtbt | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 2 |
Base type:
| |
Applies to
| nviHwGasDetection | Array:
| not permitted | Default:
| 30,0 |
|
cpAlarmTriggerState | Alarm Trigger state.:
This input configuration indicates the default state of the input signal. With this configuration property you could set if the alarm signal will be defected while ACTIVE HIGH or ACTIVE LOW.
|
|
Optional Configuration Properties |
nciLocation | Location: Provides descriptive physical location information related to the object.
|
|