SFPThardwiredRecirculation

Hardwired Recirculation profile..  The hardwired Recirculation profile is used to monitor a Hardwired Recirculation input. 
 

Network Variables

Configuration Properties

nviHwRecircula
nvoHwRecirculaFb

cpAlarmTriggerState
cpMaxSendTime
cpReceiveHrtbt

nciLocation

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 105
Obsolete: no
Key: 4312
Inheriting: no


Mandatory Network Variables

nviHwRecirculaRecirculation Input.:   This input network variable is used to put the system on Recirculation. 
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nvoHwRecirculaFbRecirculation Output.:   This output network variable is used to indicate that a system is on Recirculation. 
Member Number: 2
Base type:
SNVT_switch
Direction: output
Service: acknowledged


Mandatory Configuration Properties

cpMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 1
Base type:
SCPTmaxSendTime
Applies to nvoHwRecirculaFb
Array: not permitted
Default: 30,0
cpReceiveHrtbtMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 2
Base type:
SCPTmaxRcvTime
Applies to nviHwRecircula
Array: not permitted
Default: 30,0
cpAlarmTriggerStateAlarm Trigger state.:   This input configuration indicates the default state of the input signal. With this configuration property you could set if the alarm signal will be defected while ACTIVE HIGH or ACTIVE LOW.  
Member Number: 3
Base type:
SCPTdefltBehave
Applies to SFPThardwiredRecirculation
Array: not permitted
Default: 100,0 1


Optional Configuration Properties

nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 4
Base type:
SCPTlocation
Applies to SFPThardwiredRecirculation
Array: not permitted
Default: 00*31