HVAC Temperature Sensor.. Temperature sensor designed for HVAC applications.
|
| |
Network Variables | Configuration Properties |
nvoHVACTemp
nvoFixPtTemp nvoFloatTemp
| nciMaxSendTime nciMinDelta nciMinSendTime
nciTmpOffset
|
| |
Details: |
| Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
| Index:
| 9 |
| Obsolete:
| no |
| Key:
| 1040 |
|
Inheriting:
| no |
|
Principal Variable
| nvoHVACTemp |
Mandatory Network Variables |
| nvoHVACTemp | Temperature: The temperature of the sensor using HVAC temperature data type.
|
| Member Number:
| 1 | |
Base type:
| | | Direction:
| output | | Service:
| any |
|
Optional Network Variables |
| nvoFixPtTemp | Temperature: The temperature of the sensor using fixed point data type.
|
| Member Number:
| 2 | |
Base type:
| | | Direction:
| output | | Service:
| any |
|
| nvoFloatTemp | Temperature: The temperature of the sensor using floating point data type.
|
| Member Number:
| 3 | |
Base type:
| | | Direction:
| output | | Service:
| any |
|
Mandatory Configuration Properties |
| nciMaxSendTime | Maximum send time.: Controls the maximum period of time before the output values are transmitted.
|
| Member Number:
| 1 | |
Base type:
| | |
Applies to
| SFPThvacTempSensor | | Array:
| not permitted | | Default:
| 300,0 |
|
| nciMinSendTime | Minimum send time.: Controls the minimum period of time between output value transmissions.
|
|
| nciMinDelta | Send on delta.: The minimum change required to force transmission of the output value.
|
| Member Number:
| 3 | |
Base type:
| | |
Applies to
| nvoHVACTemp | | Array:
| not permitted | | Default:
| 0,30 |
|
Optional Configuration Properties |
| nciTmpOffset | Temperature offset.: Used to calibrate external hardware with additive offset after transformation.
|
| Member Number:
| 4 | |
Base type:
| | |
Applies to
| nvoHVACTemp | | Array:
| not permitted |
|