Lamp Actuator.. Used within devices that can control the illumination level of a lamp.
|
| |
Network Variables | Configuration Properties |
nviLampValue nvoLampValueFb
nvoEnergyCnt nvoRunHours
| ncRunHrAlarm nciDefault nciEnergyCntInit nciInFbDly nciLocation nciRunHrInit
|
| |
Details: |
| Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
| Index:
| 16 |
| Obsolete:
| no |
| Key:
| 3040 |
|
Inheriting:
| no |
|
Principal Variable
| nviLampValue |
Mandatory Network Variables |
| nviLampValue | Lamp input value.: Permits another device to pass data to the Lamp Actuator.
|
| Member Number:
| 1 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nvoLampValueFb | Lamp feedback output.: State of the Lamp Actuator (ON or OFF) and the percentage level of intensity.
|
| Member Number:
| 2 | |
Base type:
| | | Direction:
| output | | Service:
| any |
|
Optional Network Variables |
| nvoRunHours | Running hours output.: Monitors the Lamp Actuator's running (ON) hours.
|
| Member Number:
| 3 | |
Base type:
| | | Direction:
| output | | Service:
| any |
|
| nvoEnergyCnt | Energy counter output.: Monitors the consumed energy in kiloWatt hours.
|
| Member Number:
| 4 | |
Base type:
| | | Direction:
| output | | Service:
| any |
|
Optional Configuration Properties |
| nciLocation | Location label.: Provides descriptive physical location information related to the object.
|
|
| nciInFbDly | Input-value feedback delay.: The time period after the last update, in a succession of changes to the input, before the feedback output is updated.
|
| Member Number:
| 2 | |
Base type:
| | |
Applies to
| nvoLampValueFb | | Array:
| not permitted | | Default:
| 0 0:0:0:300 |
|
| nciDefault | Default output.: The level the sensor should adopt in certain default conditions.
|
| Member Number:
| 3 | |
Base type:
| | |
Applies to
| nvoLampValueFb | | Array:
| not permitted |
|
| nciRunHrInit | Initialization of running hours counter.:
|
| Member Number:
| 4 | |
Base type:
| | |
Applies to
| nvoRunHours | | Array:
| not permitted |
|
| ncRunHrAlarm | Alarm threshold level for the running hours counter.:
|
| Member Number:
| 5 | |
Base type:
| | |
Applies to
| nvoRunHours | | Array:
| not permitted |
|
| nciEnergyCntInit | Initialization of energy counter.:
|
| Member Number:
| 6 | |
Base type:
| | |
Applies to
| nvoEnergyCnt | | Array:
| not permitted |
|