SFPTtimeProgram

Time program..   

A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure. The Web Link is:

VDI - Room control functions (RA functions)
 

Network Variables

Configuration Properties

nvoSchedValue

nviTimeSet

cpNVType

cpMaxNVLength

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 130
Obsolete: no
Key: 16503
Inheriting: no


Mandatory Network Variables

nvoSchedValueScheduled value.:    
Member Number: 1
Base type:
SNVT_xxx
Direction: output
Service: any


Optional Network Variables

nviTimeSetTime stamp.:    
Member Number: 2
Base type:
SNVT_time_stamp
Direction: input
Service: any


Mandatory Configuration Properties

cpNVTypeNetwork variable type.:   Network variable type for network variables that support changeable types. 
Member Number: 1
Base type:
SCPTnvType
Applies to nvoSchedValue
Array: not permitted
Default: PID 0:0:0:0:0:0:0:0, Scope 0, Index 1, NVT_CAT_INITIAL, 1 bytes, A=0, B=0, C=0


Optional Configuration Properties

cpMaxNVLengthMaximum network variable length.:   Maximum length of a type that may be assigned to the network variable. 
Member Number: 2
Base type:
SCPTmaxNVLength
Applies to SFPTtimeProgram
Array: not permitted
Default: 0