SFPTutilityDataLoggerRegister

Utility Data-Logger Register..  Used to report energy use from an energy meter. 
 

Network Variables

Configuration Properties

nvoRegVal

nviEndPeriod
nviHistChoice
nviHistTime
nviRegState
nviRegVal
nvoHistTime
nvoHistVal
nvoMeasPeriod

nciBaseValue
nciHLimit
nciRegName
nciSendOnDelta

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 71
Obsolete: no
Key: 2110
Inheriting: no
Principal Variable nvoRegVal


Mandatory Network Variables

nvoRegValRegister value output.:   This network variable contains the current value of the register with a time stamp and status bits all contained within one variab. 
Member Number: 1
Base type:
SNVT_reg_val_ts
Direction: output
Service: any


Optional Network Variables

nviHistChoiceRegister historical period selection input.:   This input network variable controls which history value is shown on the output network variable side via the network variables voHistVal and nvoHistTime. 
Member Number: 2
Base type:
SNVT_count
Direction: input
Service: any
nviHistTimeRegister historical time selection input.:   This input network variable controls, according to the time, which history value is shown on the output network variable side via the network variables nvoHistVal and nvoHistTime.  
Member Number: 3
Base type:
SNVT_time_stamp
Direction: input
Service: any
nviRegValRegister value input.:   A value can be sent to the register object via the network using this network variable. 
Member Number: 4
Base type:
SNVT_reg_val
Direction: input
Service: any
nviRegStateRegister state selection input.:   The register can be activated or deactivated by using this variable. When a register is activated the register object measures into the register. If the register is deactivated it does not measure but it is read/write-able.  
Member Number: 5
Base type:
SNVT_lev_disc
Direction: input
Service: any
nviEndPeriodMeasuring period ending input.:   This input network variable controls the ending of a billing period. When the billing period is terminated, the current register value will be transferred to the next history register. The series register cannot use this roperty.  
Member Number: 6
Base type:
SNVT_time_stamp
Direction: input
Service: any
nvoHistValRegister historical value output.:   This output network variable contains the register object's historical value of a chosen time or history period. The output value is selected using the nviHistChoice or nviHistTime variables.  
Member Number: 7
Base type:
SNVT_reg_val_ts
Direction: output
Service: any
nvoHistTimeRegister historical time output.:   This output network variable contains a billing period end time. The output value is selected using the nviHistChoice and nviHistTime variables. 
Member Number: 8
Base type:
SNVT_time_stamp
Direction: output
Service: any
nvoMeasPeriodRegister measuring period output.:   This output network variable contains the length of the measuring period. If used, the register object measures series or maximum value data. Otherwise the value is zero.  
Member Number: 9
Base type:
SNVT_elapsed_tm
Direction: output
Service: any


Optional Configuration Properties

nciRegNameRegister name.:   The name of a utility data logger register device. 
Member Number: 1
Base type:
SCPTregName
Applies to SFPTutilityDataLoggerRegister
Array: not permitted
Default: 00*31
nciHLimitHigh limit 1.:   The alarm high limit against which the value field of the output value is tested for alarm conditions. 
Member Number: 2
Base type:
SCPThighLimit1
Applies to SFPTutilityDataLoggerRegister
Array: not permitted
Default: 00*4
nciSendOnDeltaSend on delta.:   The minimum change required to force transmission of the output value. 
Member Number: 3
Base type:
SCPTsndDelta
Applies to SFPTutilityDataLoggerRegister
Array: not permitted
Default: 00*4
nciBaseValueBase value.:   The base value (where to begin counting) 
Member Number: 4
Base type:
SCPTbaseValue
Applies to SFPTutilityDataLoggerRegister
Array: not permitted
Default: 0 RVU_NONE 0