SNVT_hvac_satsts

Overview:

HVAC saturation status..  A value of 0 in a field indicates that the resource associated with that field has not saturated or reached an end stop before attaining the required setpoint. A value of 1 indicates that the resource associated with that field has saturated or reached an end stop without attaining the required setpoint.  

A value of 0 indicates that the resource associated with that field has not saturated or reached an end stop before attaining the required setpoint. A value of 1 indicates that the resource associated with that field has saturated or reached an end stop without attaining the required setpoint.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 172
Obsolete: no
Size: 2
Programmatic Name: SNVT_hvac_satsts
Neuron C Type:
Structure
pri_heatPrimary heating saturation status.  (boolean) .  A value of 0 indicates primary heating is not saturated. A value of 1 indicates primary heating is saturated. 
 
bitfield
Signed: no
Width: 1
Offset: 0
Minimum: 0
Maximum: 1
Scaling (A,B,C): 1,  0,  0
Scaled value: 1 *10 0 *(Raw+0)
Resolution: 1
sec_heatSecondary heating saturation status.  (boolean) .  A value of 0 indicates secondary heating is not saturated. A value of 1 indicates secondary heating is saturated. 
 
bitfield
Signed: no
Width: 1
Offset: 1
Minimum: 0
Maximum: 1
Scaling (A,B,C): 1,  0,  0
Scaled value: 1 *10 0 *(Raw+0)
Resolution: 1
pri_coolPrimary cooling saturation status.  (boolean) .  A value of 0 indicates primary cooling is not saturated. A value of 1 indicates primary cooling is saturated. 
 
bitfield
Signed: no
Width: 1
Offset: 2
Minimum: 0
Maximum: 1
Scaling (A,B,C): 1,  0,  0
Scaled value: 1 *10 0 *(Raw+0)
Resolution: 1
sec_coolSecondary cooling saturation status.  (boolean) .  A value of 0 indicates secondary cooling is not saturated. A value of 1 indicates secondary cooling is saturated. 
 
bitfield
Signed: no
Width: 1
Offset: 3
Minimum: 0
Maximum: 1
Scaling (A,B,C): 1,  0,  0
Scaled value: 1 *10 0 *(Raw+0)
Resolution: 1
pri_duct_starvedPrimary duct saturation status.  (boolean) .  A value of 0 indicates primary duct is not saturated (starved). A value of 1 indicates primary duct is saturated (starved). 
 
bitfield
Signed: no
Width: 1
Offset: 4
Minimum: 0
Maximum: 1
Scaling (A,B,C): 1,  0,  0
Scaled value: 1 *10 0 *(Raw+0)
Resolution: 1
sec_duct_starvedSecondary duct saturation status.  (boolean) .  A value of 0 indicates secondary duct is not saturated (starved). A value of 1 indicates secondary duct is saturated (starved). 
 
bitfield
Signed: no
Width: 1
Offset: 5
Minimum: 0
Maximum: 1
Scaling (A,B,C): 1,  0,  0
Scaled value: 1 *10 0 *(Raw+0)
Resolution: 1
reserved.   
 
bitfield
Signed: no
Width: 2
Offset: 6
Minimum: 0
Maximum: 3
Scaling (A,B,C): 1,  0,  0
Scaled value: 1 *10 0 *(Raw+0)
Resolution: 1
reserved1.   
 
bitfield
Signed: no
Width: 4
Offset: 0
Minimum: 0
Maximum: 15
Scaling (A,B,C): 1,  0,  0
Scaled value: 1 *10 0 *(Raw+0)
Resolution: 1
manufacturer_definedManufacturer defined.  (boolean) .  Four manufacturer-defined bits -- please see product documentation for proper interpretation of these bits. 
 
bitfield
Signed: no
Width: 4
Offset: 4
Minimum: 0
Maximum: 15
Scaling (A,B,C): 1,  0,  0
Scaled value: 1 *10 0 *(Raw+0)
Resolution: 1
Formats:

SNVT_hvac_satsts:  text("%d %d %d %d %d %d %d", pri_heat, sec_heat, pri_cool, sec_cool, pri_duct_starved, sec_duct_starved, manufacturer_defined)