Damper Actuator.. Three sub types of HVAC actuators can be handled by this object: general purpose, fire & smoke, and airflow control.
|
|
Network Variables | Configuration Properties |
nviActuatState nviRelStpt nvoActualValue
nviEmergOvrd nviManOvrd nvoAbsAirFlow nvoAbsAngle nvoActuatStateFb nvoDuctTemp nvoEmergOvrdFb nvoRelStptFb
| nciDirection nciMaxSendTime nciMinSendTime nciRcvTime
nciActuatType nciDriveTime nciDuctSize nciLocation nciMaxSetpoint nciMinSetpoint nciNomAirFlow nciNomAngle nciOemType nciSendOnDltAngl nciSendOnDltFlow nciSendOnDltTemp nciTempSensConst nciVavSensConst
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 37 |
Obsolete:
| no |
Key:
| 8110 |
Inheriting:
| no |
Mandatory Network Variables |
nviRelStpt | Actuator setpoint input.: Controls the relative actuator setpoint.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nviActuatState | Actuator state input.: Used where the actuator is connected to a switch that forces the actuator to a predefined set of positions or air volumes.
|
Member Number:
| 2 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoActualValue | Actual position output.: Present position of the actuator.
|
Member Number:
| 3 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
Optional Network Variables |
nviEmergOvrd | Emergency override input.: Used in fire and smoke applications to open and close an actuator with maximum speed; this input has highest priority.
|
Member Number:
| 4 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviManOvrd | Manual override input.: Command the actuator into a manual mode (mainly used during balancing)
|
Member Number:
| 5 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoActuatStateFb | Actuator state feedback output.: Mirrors the actual value of nviActuatState.
|
Member Number:
| 6 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoRelStptFb | Actuator setpoint feedback output.: Mirrors the actual value of nviRelStpt.
|
Member Number:
| 7 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoAbsAngle | Damper angle output.: Present position of the actuator's shaft or damper blade.
|
Member Number:
| 8 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoAbsAirFlow | Air flow output.: Airflow through the associated VAV box.
|
Member Number:
| 9 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoDuctTemp | Inside duct temperature output.: Present temperature inside the duct.
|
Member Number:
| 10 |
Base type:
| | Direction:
| output | Service:
| any | Minimum:
| -50,00 | Maximum:
| 150,00 |
|
nvoEmergOvrdFb | Emergency override feedback output.: Mirrors the value of nviEmergOvrd.
|
Member Number:
| 11 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
Mandatory Configuration Properties |
nciMinSendTime | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
Member Number:
| 1 |
Base type:
| |
Applies to
| SFPTdamperActuator | Array:
| not permitted | Default:
| 30,0 |
|
nciMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
|
nciRcvTime | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
|
nciDirection | Direction / Safety position.: The actuator sense of rotation and safety position; bit 0 set => counterclockwise, bit 1 set => damper open.
|
Member Number:
| 4 |
Base type:
| |
Applies to
| SFPTdamperActuator | Array:
| not permitted | Default:
| 0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0 |
|
Optional Configuration Properties |
nciSendOnDltFlow | Flow send on delta.: The minimum change in airflow required to be treated as significant.
|
Member Number:
| 5 |
Base type:
| |
Applies to
| nvoAbsAirFlow | Array:
| not permitted | Default:
| 10 |
|
nciSendOnDltTemp | Minimum delta temperature.: The minimum change in temperature required to be treated as significant.
|
Member Number:
| 6 |
Base type:
| |
Applies to
| nvoDuctTemp | Array:
| not permitted | Minimum:
| 0,00 | Default:
| 1,00 |
|
nciSendOnDltAngl | Damper angle send on delta.: The minimum change in damper actuator angle required to be treated as significant.
|
Member Number:
| 7 |
Base type:
| |
Applies to
| nvoAbsAngle | Array:
| not permitted | Minimum:
| 0,00 | Default:
| 5,00 |
|
nciActuatType | Actuator label.: The identification of the exact actuator type or label.
|
Member Number:
| 8 |
Base type:
| |
Applies to
| SFPTdamperActuator | Flags:
| manufacturer specific | Array:
| not permitted |
|
nciOemType | OEM label.: The label, programmed by the OEM, to identify the unit name.
|
Member Number:
| 9 |
Base type:
| |
Applies to
| SFPTdamperActuator | Flags:
| device specific, constant | Array:
| not permitted |
|
nciLocation | Location: Provides descriptive physical location information related to the object.
|
|
nciDriveTime | Drive time.: The transition time for a full 100% stroke (change from one extreme to the other)
|
Member Number:
| 11 |
Base type:
| |
Applies to
| SFPTdamperActuator | Array:
| not permitted | Default:
| 150,0 |
|
nciNomAngle | Nominal angle.: The nominal angle for an actuator.
|
Member Number:
| 12 |
Base type:
| |
Applies to
| SFPTdamperActuator | Array:
| not permitted | Minimum:
| 0,00 | Maximum:
| 95,00 | Default:
| 90,00 |
|
nciNomAirFlow | Nominal air flow.: Value used in calculating the air flow in an airflow control actuator.
|
|
nciDuctSize | Duct area or size.: The duct area used to calculate the air flow, relevant only for VAV actuators / controllers.
|
|
nciMaxSetpoint | Maximum range.: The maximum limit of the value of the primary output network variable for the object.
|
Member Number:
| 15 |
Base type:
| |
Applies to
| nvoActualValue | Array:
| not permitted | Default:
| 00*2-4E-20 |
|
nciMinSetpoint | Minimum range.: The minimum limit of the value of the primary output network variable for the object.
|
Member Number:
| 16 |
Base type:
| |
Applies to
| nvoActualValue | Array:
| not permitted |
|
nciVavSensConst | VAV sensor constant.: Calibration constant used to calculate airflow.
|
|
nciTempSensConst | Temperature sensor constant.: Calibration value for a duct temperature sensor.
|
|