Fire Smoke Damper Actuator.. Used to expell smoke or control fire-spread by manipulating the actuator position on a damper.
|
| |
Network Variables | Configuration Properties |
nviActuDrive nvoActuPosn
nvoActuDriveFb
| nciDriveT nciRcvrHrtBt nciSafetyPosn nciTurnOffT nciZoneNum
nciActuLabel nciInstallDate nciLocation nciMaintDate nciManfDate nciMaxSendTime nciOEMLable
|
| |
Details: |
| Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
| Index:
| 59 |
| Obsolete:
| no |
| Key:
| 11001 |
|
Inheriting:
| no |
Mandatory Network Variables |
| nviActuDrive | Actuator Drive.: Controls the actuator position.
|
| Member Number:
| 1 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nvoActuPosn | HVAC emergency mode.:
|
| Member Number:
| 2 | |
Base type:
| | | Direction:
| output | | Service:
| acknowledged |
|
Optional Network Variables |
| nvoActuDriveFb | Actuator Drive Feedback.: Reflects the actuator value of nviActuDrive. Used to synchronize source objects in multiple relationships.
|
| Member Number:
| 3 | |
Base type:
| | | Direction:
| output | | Service:
| acknowledged |
|
Mandatory Configuration Properties |
| nciDriveT | Drive time.: The transition time for a full 100% stroke (change from one extreme to the other)
|
|
| nciRcvrHrtBt | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
| Member Number:
| 2 | |
Base type:
| | |
Applies to
| nviActuDrive | | Array:
| not permitted | | Default:
| 0,0 |
|
| nciSafetyPosn | Direction / Safety position.: The actuator sense of rotation and safety position; bit 0 set => counterclockwise, bit 1 set => damper open.
|
| Member Number:
| 3 | |
Base type:
| | |
Applies to
| SFPTfireSmokeDamperActuator | | Array:
| not permitted | | Default:
| 0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0 |
|
| nciTurnOffT | Turn-off delay.: The length of time that the load remains energized after a change from ON to OFF has been received.
|
|
| nciZoneNum | Zone number.: The zone number for the device.
|
|
Optional Configuration Properties |
| nciActuLabel | Actuator label.: The identification of the exact actuator type or label.
|
|
| nciInstallDate | Installation date.: The date of installation for the device.
|
|
| nciLocation | Location: Provides descriptive physical location information related to the object.
|
|
| nciMaintDate | Maintenance date.: The date of last maintenance for the device.
|
|
| nciManfDate | Manufacture date.: The date of manufacture for the device.
|
| Member Number:
| 10 | |
Base type:
| | |
Applies to
| SFPTfireSmokeDamperActuator | | Flags:
| manufacturer specific | | Array:
| not permitted | | Default:
| 0/0/0 0:0:0 |
|
| nciOEMLable | OEM label.: The label, programmed by the OEM, to identify the unit name.
|
| Member Number:
| 11 | |
Base type:
| | |
Applies to
| SFPTfireSmokeDamperActuator | | Flags:
| manufacturer specific | | Array:
| not permitted | | Minimum:
| 00*31 | | Maximum:
| FF*16-00*15 | | Default:
| 00*31 |
|
| nciMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
| Member Number:
| 12 | |
Base type:
| | |
Applies to
| nvoActuDriveFb | | Array:
| not permitted | | Default:
| 0,0 |
|