SFPTaudibleFireIndicator

Audible Fire Indicator..  Indicator of the presence of fire by audible (siren/bell) means. 
 

Network Variables

Configuration Properties

nviFireAudible
nvoFireTrouble

nvoFireAudible

nciAudibleOut
nciMaxReceiveT
nciNodeLocation
nciZoneNum

nciFireText1
nciFireText2
nciFireText3
nciIndicatorType
nciInstallDate
nciMaintDate
nciManufDate
nciMaxSendTime
nciOEMLabel

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 63
Obsolete: no
Key: 11006
Inheriting: no


Mandatory Network Variables

nviFireAudibleFire Audible Input.:   This input network variable receives the status (ON or OFF) request (command) for an audible indicating device. It can be bound to the nvoAlarm network variable(s) of initiating device(s)  
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nvoFireTroubleSwitch:    
Member Number: 2
Base type:
SNVT_switch
Direction: output
Service: acknowledged


Optional Network Variables

nvoFireAudibleFire Audible Feedback.:   This output network variable transmits the feedback status (ON or OFF) of indicating device. 
Member Number: 3
Base type:
SNVT_switch
Direction: output
Service: acknowledged


Mandatory Configuration Properties

nciNodeLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 1
Base type:
SCPTlocation
Applies to SFPTaudibleFireIndicator
Flags: modify when disabled
Array: not permitted
Default: 00*31
nciMaxReceiveTMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 2
Base type:
SCPTmaxRcvTime
Applies to SFPTaudibleFireIndicator
Array: not permitted
Default: 0,0
nciZoneNumZone number.:   The zone number for the device. 
Member Number: 3
Base type:
SCPTzoneNum
Applies to SFPTaudibleFireIndicator
Array: not permitted
Default: 0
nciAudibleOutAudible sound output intensity.:   Audible sound output intensity specification of the device at 1 meter distant. 
Member Number: 4
Base type:
SCPTaudOutput
Applies to SFPTaudibleFireIndicator
Flags: manufacturer specific, constant
Array: not permitted
Default: 0,00


Optional Configuration Properties

nciOEMLabelOEM label.:   The label, programmed by the OEM, to identify the unit name. 
Member Number: 5
Base type:
SCPToemType
Applies to SFPTaudibleFireIndicator
Flags: manufacturer specific, constant
Array: not permitted
Minimum: 00*31
Maximum: FF*16-00*15
Default: 00*31
nciInstallDateInstallation date.:   The date of installation for the device. 
Member Number: 6
Base type:
SCPTinstallDate
Applies to SFPTaudibleFireIndicator
Flags: modify when disabled
Array: not permitted
Default: 0/0/0 0:0:0
nciMaintDateMaintenance date.:   The date of last maintenance for the device. 
Member Number: 7
Base type:
SCPTmaintDate
Applies to SFPTaudibleFireIndicator
Array: not permitted
Default: 0/0/0 0:0:0
nciManufDateManufacture date.:   The date of manufacture for the device. 
Member Number: 8
Base type:
SCPTmanfDate
Applies to SFPTaudibleFireIndicator
Flags: manufacturer specific, constant
Array: not permitted
Default: 0/0/0 0:0:0
nciFireText1Fire text information.:   Text information relevant to fire conditions. A '>' at end of string indicates presence of fire text 2. 
Member Number: 9
Base type:
SCPTfireTxt1
Applies to SFPTaudibleFireIndicator
Flags: modify when disabled
Array: not permitted
Minimum: 00*31
Maximum: FF*30-00
Default: 00*31
nciFireText2Fire text information, continuation.:   Continuation text information relevant to fire conditions. A '>' at end of string indicates presence of fire text 3. 
Member Number: 10
Base type:
SCPTfireTxt2
Applies to SFPTaudibleFireIndicator
Flags: modify when disabled
Array: not permitted
Minimum: 00*31
Maximum: FF*30-00
Default: 00*31
nciFireText3Fire text information, second continuation.:   Second continuation text information relevant to fire conditions. 
Member Number: 11
Base type:
SCPTfireTxt3
Applies to SFPTaudibleFireIndicator
Flags: modify when disabled
Array: not permitted
Minimum: 00*31
Maximum: FF*30-00
Default: 00*31
nciMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 12
Base type:
SCPTmaxSendTime
Applies to SFPTaudibleFireIndicator
Array: not permitted
Default: 0,0
nciIndicatorTypeFire indicator device type.:   Describes the fire indicator device. 
Member Number: 13
Base type:
SCPTfireIndicate
Applies to SFPTaudibleFireIndicator
Array: not permitted
Default: FN_UNDEFINED