Heat-Pump Controller.. Used to control an HVAC heat-pump space-conditioning unit.
|
|
Network Variables | Configuration Properties |
nviSetPoint nviSpaceTemp nvoSpaceTemp nvoUnitStatus
nviApplicMode nviAuxHeat nviOccCmd nviOccupSw nviSetPtOffset nvoEffectSetPt
| nciSndHrtBt nciTempSetpts
nciLocation nciRcvHrtBt nciRcvHrtBtNV01 nciRcvHrtBtNV02 nciRcvHrtBtNV05 nciRcvHrtBtNV06 nciRcvHrtBtNV07 nciRcvHrtBtNV08 nciRcvHrtBtNV09 nciSndHrtBtNV03 nciSndHrtBtNV04 nciSndHrtBtNV10
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 51 |
Obsolete:
| no |
Key:
| 8051 |
Inheriting:
| no |
Mandatory Network Variables |
nviSpaceTemp | Remote Space Temperature.: This input network variable is used to connect an external space temperature sensor to the node.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviSetPoint | Setpoint from Network.: This input network variable is used to allow the emperature setpoint for the occupied mode to be changed via the network.
|
Member Number:
| 2 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoSpaceTemp | Space Temp Value Used.: This output network variable is used to send the value of the controlled space temperature to other nodes.
|
Member Number:
| 3 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoUnitStatus | Current Status of Unit.: This output network variable is available to report the object status.
|
Member Number:
| 4 |
Base type:
| | Direction:
| output | Service:
| any |
|
Optional Network Variables |
nviApplicMode | Command from System.: This network variable input is used to coordinate the Heat Pump with any supervisory controller or intelligent human interface device.
|
Member Number:
| 5 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviOccCmd | HVAC Occupancy Status.: This input network variable is used to place the heat pump into different occupancy modes. It is typically set by a supervisory node.
|
Member Number:
| 6 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviOccupSw | Simple Occupancy Status.: This input network variable provides an indication of the simple two-state occupancy status of the unit, which is either unoccupied or occupied.
|
Member Number:
| 7 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviSetPtOffset | Setpoint Offset.: This input network variable specifies the direction and magnitude of the shift of the current occupied setpoints.
|
Member Number:
| 8 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviAuxHeat | Auxilliary Heat Enable.: This input network variable indicates whether auxilliary heat has been enabled or disabled.
|
Member Number:
| 9 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoEffectSetPt | Setpoint Value Used.: This input network variable provides an indication of the setpoint being used for control.
|
Member Number:
| 10 |
Base type:
| | Direction:
| output | Service:
| any |
|
Mandatory Configuration Properties |
nciTempSetpts | Occupancy temperature setpoints.: The occupancy temperature setpoints for heat and cool mode.
|
Member Number:
| 1 |
Base type:
| |
Applies to
| SFPTheatPump | Array:
| not permitted | Minimum:
| -10,00,-10,00,-10,00,-10,00,-10,00,-10,00 | Maximum:
| 35,00,35,00,35,00,35,00,35,00,35,00 | Default:
| 23,00,25,00,28,00,21,00,19,00,16,00 |
|
nciSndHrtBt | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 13 |
Base type:
| |
Applies to
| SFPTheatPump | Array:
| not permitted | Default:
| 0,0 |
|
Optional Configuration Properties |
nciSndHrtBtNV10 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 4 |
Base type:
| |
Applies to
| nvoEffectSetPt | Array:
| not permitted | Default:
| 0,0 |
|
nciLocation | Location: Provides descriptive physical location information related to the object.
|
Member Number:
| 5 |
Base type:
| |
Applies to
| SFPTheatPump | Array:
| not permitted | Default:
| 00*31 |
|
nciRcvHrtBtNV01 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 6 |
Base type:
| |
Applies to
| nviSpaceTemp | Array:
| not permitted | Default:
| 0,0 |
|
nciRcvHrtBtNV02 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 7 |
Base type:
| |
Applies to
| nviSetPoint | Array:
| not permitted | Default:
| 0,0 |
|
nciRcvHrtBtNV05 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 8 |
Base type:
| |
Applies to
| nviApplicMode | Array:
| not permitted | Default:
| 0,0 |
|
nciRcvHrtBtNV06 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 9 |
Base type:
| |
Applies to
| nviOccCmd | Array:
| not permitted | Default:
| 0,0 |
|
nciRcvHrtBtNV07 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 10 |
Base type:
| |
Applies to
| nviOccupSw | Array:
| not permitted | Default:
| 0,0 |
|
nciRcvHrtBtNV08 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 11 |
Base type:
| |
Applies to
| nviSetPtOffset | Array:
| not permitted | Default:
| 0,0 |
|
nciRcvHrtBtNV09 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 12 |
Base type:
| |
Applies to
| nviAuxHeat | Array:
| not permitted | Default:
| 0,0 |
|
nciSndHrtBtNV03 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 14 |
Base type:
| |
Applies to
| nvoSpaceTemp | Array:
| not permitted | Default:
| 0,0 |
|
nciSndHrtBtNV04 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 15 |
Base type:
| |
Applies to
| nvoUnitStatus | Array:
| not permitted | Default:
| 0,0 |
|
nciRcvHrtBt | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 16 |
Base type:
| |
Applies to
| SFPTheatPump | Array:
| not permitted | Default:
| 0,0 |
|