SFPTheatPump

Heat-Pump Controller..  Used to control an HVAC heat-pump space-conditioning unit. 
 

Network Variables

Configuration Properties

nviSetPoint
nviSpaceTemp
nvoSpaceTemp
nvoUnitStatus

nviApplicMode
nviAuxHeat
nviOccCmd
nviOccupSw
nviSetPtOffset
nvoEffectSetPt

nciSndHrtBt
nciTempSetpts

nciLocation
nciRcvHrtBt
nciRcvHrtBtNV01
nciRcvHrtBtNV02
nciRcvHrtBtNV05
nciRcvHrtBtNV06
nciRcvHrtBtNV07
nciRcvHrtBtNV08
nciRcvHrtBtNV09
nciSndHrtBtNV03
nciSndHrtBtNV04
nciSndHrtBtNV10

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 51
Obsolete: no
Key: 8051
Inheriting: no


Mandatory Network Variables

nviSpaceTempRemote Space Temperature.:   This input network variable is used to connect an external space temperature sensor to the node. 
Member Number: 1
Base type:
SNVT_temp_p
Direction: input
Service: any
nviSetPointSetpoint from Network.:   This input network variable is used to allow the emperature setpoint for the occupied mode to be changed via the network. 
Member Number: 2
Base type:
SNVT_temp_p
Direction: input
Service: any
nvoSpaceTempSpace Temp Value Used.:   This output network variable is used to send the value of the controlled space temperature to other nodes. 
Member Number: 3
Base type:
SNVT_temp_p
Direction: output
Service: any
nvoUnitStatusCurrent Status of Unit.:   This output network variable is available to report the object status. 
Member Number: 4
Base type:
SNVT_hvac_status
Direction: output
Service: any


Optional Network Variables

nviApplicModeCommand from System.:   This network variable input is used to coordinate the Heat Pump with any supervisory controller or intelligent human interface device. 
Member Number: 5
Base type:
SNVT_hvac_mode
Direction: input
Service: any
nviOccCmdHVAC Occupancy Status.:   This input network variable is used to place the heat pump into different occupancy modes. It is typically set by a supervisory node. 
Member Number: 6
Base type:
SNVT_occupancy
Direction: input
Service: any
nviOccupSwSimple Occupancy Status.:   This input network variable provides an indication of the simple two-state occupancy status of the unit, which is either unoccupied or occupied. 
Member Number: 7
Base type:
SNVT_switch
Direction: input
Service: any
nviSetPtOffsetSetpoint Offset.:   This input network variable specifies the direction and magnitude of the shift of the current occupied setpoints. 
Member Number: 8
Base type:
SNVT_temp_p
Direction: input
Service: any
nviAuxHeatAuxilliary Heat Enable.:   This input network variable indicates whether auxilliary heat has been enabled or disabled. 
Member Number: 9
Base type:
SNVT_switch
Direction: input
Service: any
nvoEffectSetPtSetpoint Value Used.:   This input network variable provides an indication of the setpoint being used for control. 
Member Number: 10
Base type:
SNVT_temp_p
Direction: output
Service: any


Mandatory Configuration Properties

nciTempSetptsOccupancy temperature setpoints.:   The occupancy temperature setpoints for heat and cool mode. 
Member Number: 1
Base type:
SCPTsetPnts
Applies to SFPTheatPump
Array: not permitted
Minimum: -10,00,-10,00,-10,00,-10,00,-10,00,-10,00
Maximum: 35,00,35,00,35,00,35,00,35,00,35,00
Default: 23,00,25,00,28,00,21,00,19,00,16,00
nciSndHrtBtMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 13
Base type:
SCPTmaxSendTime
Applies to SFPTheatPump
Array: not permitted
Default: 0,0


Optional Configuration Properties

nciSndHrtBtNV10Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 4
Base type:
SCPTmaxSendTime
Applies to nvoEffectSetPt
Array: not permitted
Default: 0,0
nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 5
Base type:
SCPTlocation
Applies to SFPTheatPump
Array: not permitted
Default: 00*31
nciRcvHrtBtNV01Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 6
Base type:
SCPTmaxRcvTime
Applies to nviSpaceTemp
Array: not permitted
Default: 0,0
nciRcvHrtBtNV02Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 7
Base type:
SCPTmaxRcvTime
Applies to nviSetPoint
Array: not permitted
Default: 0,0
nciRcvHrtBtNV05Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 8
Base type:
SCPTmaxRcvTime
Applies to nviApplicMode
Array: not permitted
Default: 0,0
nciRcvHrtBtNV06Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 9
Base type:
SCPTmaxRcvTime
Applies to nviOccCmd
Array: not permitted
Default: 0,0
nciRcvHrtBtNV07Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 10
Base type:
SCPTmaxRcvTime
Applies to nviOccupSw
Array: not permitted
Default: 0,0
nciRcvHrtBtNV08Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 11
Base type:
SCPTmaxRcvTime
Applies to nviSetPtOffset
Array: not permitted
Default: 0,0
nciRcvHrtBtNV09Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 12
Base type:
SCPTmaxRcvTime
Applies to nviAuxHeat
Array: not permitted
Default: 0,0
nciSndHrtBtNV03Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 14
Base type:
SCPTmaxSendTime
Applies to nvoSpaceTemp
Array: not permitted
Default: 0,0
nciSndHrtBtNV04Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 15
Base type:
SCPTmaxSendTime
Applies to nvoUnitStatus
Array: not permitted
Default: 0,0
nciRcvHrtBtMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 16
Base type:
SCPTmaxRcvTime
Applies to SFPTheatPump
Array: not permitted