Outdoor Luminair Controller..
Overview
Use Case
Nothing defind
Data Transfer
Nothing defind
Power-up State
Nothing defind
|
|
Network Variables | Configuration Properties |
nviEnergy nviLampValue nviRunHours nvoEnvironment nvoLampValueFb nvoOLCStatus
| cpBkupSchedule cpDeviceOutSelection cpDimLowLevelLight cpEnableStatusMsg cpLampPower cpMaxLevelVolt cpMaxSendTime cpMinSendTime cpOLCLimits cpPwrUpState cpWarmUpTime
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 96 |
Obsolete:
| no |
Key:
| 3512 |
Inheriting:
| no |
Mandatory Network Variables |
nviLampValue | Lamp Value Input.: The desired state (on/off) and value (%) of the lamp bulb.
This input will drive the desired output of the lamp controller; the output being relays, a 1-to-10V control line, a foreign lighting-control connection, or direct light output.
Values of 0 to 100% represent 0 to 100% light output.
Valid Range
Default Value
Configuration Considerations
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviRunHours | Run-Hours Change.: The method used to reset or initialize the run-hours count.
This input will overwrite the cumulative run-hours counter with a new value to either clear or initialize the internal value; enabling correct fixture-life computations in cases where the lamp controller hardware has been replaced.
Valid Range
Default Value
Configuration Considerations
|
Member Number:
| 2 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviEnergy | Electricity-Used Change.: The method used to reset or initialize the electricity-consumption total.
This input will overwrite the cumulative energy-consumption counter with a new value to either clear or initialize the internal value; enabling correct energy-consumption computations in cases where the lamp controller hardware has been replaced.
Valid Range
Default Value
Configuration Considerations
|
Member Number:
| 3 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoLampValueFb | Lamp Value Output.: The actual state (on/off) and value (%) of the lamp bulb.
This output returns the actual output value of the lamp controller. In case of fixture or lamp problems/limitations, this value can differ from the desired value provided to nviLampValue.
Valid Range
Default Value
Configuration Considerations
When Transmitted
Default Service Type
|
Member Number:
| 4 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoOLCStatus | Lamp-Controller Status Output.: The data related to the internal status conditions of the lamp controller.
Valid Range
Default Value
Configuration Considerations
When Transmitted
Heartbeat set by cpMinSendTime: the time is limited to a minimum of 120 seconds. An installer or integrator can increase this time to have less traffic on the network.
Periodic sending of status can be disabled: cpEnableStatusMsg can be used to enable/disable the send-status-message flag. There will be an ANDing combination of the different bits.
Default Service Type
|
Member Number:
| 5 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoEnvironment | OLC Environment Output.:
The measured values from in and around the environment of the fixture, including mains/lamp voltages, mains/lamp currents, lamp temperature, consumed power, and power factor.
Valid Range
Default Value
Configuration Considerations
When Transmitted
Default Service Type
|
Member Number:
| 6 |
Base type:
| | Direction:
| output | Service:
| any |
|
Mandatory Configuration Properties |
cpMinSendTime | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
Valid Range
Default Value
Configuration Requirements/Restrictions
|
|
cpMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
Valid Range
Default Value
Configuration Requirements/Restrictions
|
|
cpBkupSchedule | Backup Schedule.: The On/Off schedule to be used as a default.
This defines a default on/off schedule for cases when the lamp controller detects that communication with the segment controller is lost.
If the START and the END time are the same, then there is no backup schedule defined.
Valid Range
Default Value
Configuration Requirements/Restrictions
|
|
cpLampPower | Lamp Power.: The maximum wattage of the installed bulbs.
Valid Range
Default Value
Configuration Requirements/Restrictions
|
|
cpEnableStatusMsg | Enable-Status Mask.: Determines which status information will be available and valid for the alarm fields of nvoOLCStatus.
This setting determines which status information is conveyed by nvoOLCStatus. SET ("1") means that the corresponding value will be sent. CLEARED("0") means that the corresponding value will not be sent.
Valid Range
Default Value
Configuration Requirements/Restrictions
|
Member Number:
| 5 |
Base type:
| |
Applies to
| nvoOLCStatus | Array:
| not permitted | Default:
| 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 |
|
cpDeviceOutSelection | Device Output Selection.: The type of hardware output.
This configuration property sets the hardware-output type, if the lamp controller
is capable of more than one type of output:
- OLC_DEFAULT = Standard (default)
- OLC_RELAY = Relay Actuation
- OLC_ECO_MODE = ECO Mode
- OLC_1_TO_10 = 1-to-10 Volt
- OLC_DALI = DALI
Valid Range
Default Value
Configuration Requirements/Restrictions
|
|
cpDimLowLevelLight | Dimmable Minimum.: The minimum percentage value for a dimmable lamp to remain illuminated.
This represents the minimum light-level setting possible for the lamp and equates that to the 1-10V scale. For example: if the lamp can be dimmed only to a minimum of 50% (to still maintain illumination), then a cpDimLowLevelLight value of 50% would equate to 1V on the 1-to-10 Volt output.
Valid Range
Default Value
Configuration Requirements/Restrictions
|
|
cpWarmUpTime | Minimum warm-up time.: The time it takes the lamp to warm-up to the full operating temperature.
This is the minimum time required of a lamp to remain at 100% on (e.g., 10 Volts) before the dimming command can be executed.
Valid Range
Default Value
Configuration Requirements/Restrictions
|
|
cpMaxLevelVolt | Preceivable-Maximum Control.: The maximum voltage (of the 1-10V output) needed to achieve 100% lamp-light output. In many cases, 100% is reached before the 10V-limit is reached.
Valid Range
Default Value
Configuration Requirements/Restrictions
|
|
cpOLCLimits | OLC Limits Setpoints.: This configuration property sets the limits for nvoOLCStatus.
Valid Range
Default Value
Configuration Requirements/Restrictions
|
Member Number:
| 10 |
Base type:
| |
Applies to
| nvoOLCStatus | Array:
| not permitted | Default:
| 0 0 0 0 0 0 0 0 0,00000 0,0 0,0 |
|
cpPwrUpState | OLC Powerup state.: This configuration property is be used to define the default output value on power up.
Valid Range
Default Value
Configuration Requirements/Restrictions
|
|