SFPToutdoorLuminairController

Outdoor Luminair Controller..   

Overview

Use Case

Nothing defind

Data Transfer

Nothing defind

Power-up State

Nothing defind

 

Network Variables

Configuration Properties

nviEnergy
nviLampValue
nviRunHours
nvoEnvironment
nvoLampValueFb
nvoOLCStatus

cpBkupSchedule
cpDeviceOutSelection
cpDimLowLevelLight
cpEnableStatusMsg
cpLampPower
cpMaxLevelVolt
cpMaxSendTime
cpMinSendTime
cpOLCLimits
cpPwrUpState
cpWarmUpTime

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 96
Obsolete: no
Key: 3512
Inheriting: no


Mandatory Network Variables

nviLampValueLamp Value Input.:   The desired state (on/off) and value (%) of the lamp bulb. 

This input will drive the desired output of the lamp controller; the output being relays, a 1-to-10V control line, a foreign lighting-control connection, or direct light output.

Values of 0 to 100% represent 0 to 100% light output.

Valid Range

Default Value

Configuration Considerations

Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nviRunHoursRun-Hours Change.:   The method used to reset or initialize the run-hours count. 

This input will overwrite the cumulative run-hours counter with a new value to either clear or initialize the internal value; enabling correct fixture-life computations in cases where the lamp controller hardware has been replaced.

Valid Range

Default Value

Configuration Considerations

Member Number: 2
Base type:
SNVT_time_hour_p
Direction: input
Service: any
nviEnergyElectricity-Used Change.:   The method used to reset or initialize the electricity-consumption total. 

This input will overwrite the cumulative energy-consumption counter with a new value to either clear or initialize the internal value; enabling correct energy-consumption computations in cases where the lamp controller hardware has been replaced.

Valid Range

Default Value

Configuration Considerations

Member Number: 3
Base type:
SNVT_elec_kwh_l
Direction: input
Service: any
nvoLampValueFbLamp Value Output.:   The actual state (on/off) and value (%) of the lamp bulb. 

This output returns the actual output value of the lamp controller. In case of fixture or lamp problems/limitations, this value can differ from the desired value provided to nviLampValue.

Valid Range

Default Value

Configuration Considerations

When Transmitted

Default Service Type

Member Number: 4
Base type:
SNVT_switch
Direction: output
Service: any
nvoOLCStatusLamp-Controller Status Output.:   The data related to the internal status conditions of the lamp controller. 

Valid Range

Default Value

Configuration Considerations

When Transmitted

  • Heartbeat set by cpMinSendTime: the time is limited to a minimum of 120 seconds. An installer or integrator can increase this time to have less traffic on the network.
  • Periodic sending of status can be disabled: cpEnableStatusMsg can be used to enable/disable the send-status-message flag. There will be an ANDing combination of the different bits.
  • Default Service Type

    Member Number: 5
    Base type:
    SNVT_lamp_status
    Direction: output
    Service: any
    nvoEnvironmentOLC Environment Output.:   The measured values from in and around the environment of the fixture, including mains/lamp voltages, mains/lamp currents, lamp temperature, consumed power, and power factor.  

    Valid Range

    Default Value

    Configuration Considerations

    When Transmitted

    Default Service Type

    Member Number: 6
    Base type:
    SNVT_environment
    Direction: output
    Service: any


    Mandatory Configuration Properties

    cpMinSendTimeMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 

    Valid Range

    Default Value

    Configuration Requirements/Restrictions

    Member Number: 1
    Base type:
    SCPTminSendTime
    Applies to SFPToutdoorLuminairController
    Array: not permitted
    Default: 0,0
    cpMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 

    Valid Range

    Default Value

    Configuration Requirements/Restrictions

    Member Number: 2
    Base type:
    SCPTmaxSendTime
    Applies to SFPToutdoorLuminairController
    Array: not permitted
    Default: 0,0
    cpBkupScheduleBackup Schedule.:   The On/Off schedule to be used as a default. 

    This defines a default on/off schedule for cases when the lamp controller detects that communication with the segment controller is lost.

    If the START and the END time are the same, then there is no backup schedule defined.

    Valid Range

    Default Value

    Configuration Requirements/Restrictions

    Member Number: 3
    Base type:
    SCPTbkupSchedule
    Applies to SFPToutdoorLuminairController
    Array: not permitted
    Default: 0 0 0 0
    cpLampPowerLamp Power.:   The maximum wattage of the installed bulbs. 

    Valid Range

    Default Value

    Configuration Requirements/Restrictions

    Member Number: 4
    Base type:
    SCPTlampPower
    Applies to SFPToutdoorLuminairController
    Array: not permitted
    Default: 0,0
    cpEnableStatusMsgEnable-Status Mask.:   Determines which status information will be available and valid for the alarm fields of nvoOLCStatus. 

    This setting determines which status information is conveyed by nvoOLCStatus. SET ("1") means that the corresponding value will be sent. CLEARED("0") means that the corresponding value will not be sent.

    Valid Range

    Default Value

    Configuration Requirements/Restrictions

    Member Number: 5
    Base type:
    SCPTenableStatusMsg
    Applies to nvoOLCStatus
    Array: not permitted
    Default: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
    cpDeviceOutSelectionDevice Output Selection.:   The type of hardware output. 

    This configuration property sets the hardware-output type, if the lamp controller is capable of more than one type of output:

    • OLC_DEFAULT = Standard (default)
    • OLC_RELAY = Relay Actuation
    • OLC_ECO_MODE = ECO Mode
    • OLC_1_TO_10 = 1-to-10 Volt
    • OLC_DALI = DALI

    Valid Range

    Default Value

    Configuration Requirements/Restrictions

    Member Number: 6
    Base type:
    SCPTdeviceOutSelection
    Applies to SFPToutdoorLuminairController
    Array: not permitted
    Default: OLC_DEFAULT
    cpDimLowLevelLightDimmable Minimum.:   The minimum percentage value for a dimmable lamp to remain illuminated. 

    This represents the minimum light-level setting possible for the lamp and equates that to the 1-10V scale. For example: if the lamp can be dimmed only to a minimum of 50% (to still maintain illumination), then a cpDimLowLevelLight value of 50% would equate to 1V on the 1-to-10 Volt output.

    Valid Range

    Default Value

    Configuration Requirements/Restrictions

    Member Number: 7
    Base type:
    SCPTminSetpoint
    Applies to SFPToutdoorLuminairController
    Array: not permitted
    Default: 0,000
    cpWarmUpTimeMinimum warm-up time.:   The time it takes the lamp to warm-up to the full operating temperature. 

    This is the minimum time required of a lamp to remain at 100% on (e.g., 10 Volts) before the dimming command can be executed.

    Valid Range

    Default Value

    Configuration Requirements/Restrictions

    Member Number: 8
    Base type:
    SCPTrampUpTm
    Applies to SFPToutdoorLuminairController
    Array: not permitted
    Default: 0,0
    cpMaxLevelVoltPreceivable-Maximum Control.:   The maximum voltage (of the 1-10V output) needed to achieve 100% lamp-light output. In many cases, 100% is reached before the 10V-limit is reached. 

    Valid Range

    Default Value

    Configuration Requirements/Restrictions

    Member Number: 9
    Base type:
    SCPTmaxLevelVolt
    Applies to SFPToutdoorLuminairController
    Array: not permitted
    Default: 0,0
    cpOLCLimitsOLC Limits Setpoints.:   This configuration property sets the limits for nvoOLCStatus. 

    Valid Range

    Default Value

    Configuration Requirements/Restrictions

    Member Number: 10
    Base type:
    SCPTOLCLimits
    Applies to nvoOLCStatus
    Array: not permitted
    Default: 0 0 0 0 0 0 0 0 0,00000 0,0 0,0
    cpPwrUpStateOLC Powerup state.:   This configuration property is be used to define the default output value on power up. 

    Valid Range

    Default Value

    Configuration Requirements/Restrictions

    Member Number: 11
    Base type:
    SCPTpwrUpState
    Applies to SFPToutdoorLuminairController
    Array: not permitted
    Default: 100,0 1