SFPTroofTopUnit

Roof-Top Unit Controller..  Used to control an HVAC rooftop space-conditioning unit. 
 

Network Variables

Configuration Properties

nviSetPoint
nviSpaceTemp
nvoSpaceTemp
nvoUnitStatus

nviApplicMode
nviCO2
nviEmergCmd
nviOccCmd
nviOutsideRH
nviOutsideTemp
nviSetPtOffset
nviSpaceRH
nvoCO2
nvoEffectSetPt
nvoOutsideRH
nvoOutsideTemp

nciSetPnts
nciSndHrtBt

nciCO2Limit
nciLocation
nciRcvHrtBt
nciRcvHrtBtNV01
nciRcvHrtBtNV05
nciRcvHrtBtNV07
nciRcvHrtBtNV08
nciRcvHrtBtNV09
nciRcvHrtBtNV13
nciRcvHrtBtNV14
nciSndHrtBtNV10
nciSndHrtBtNV11
nciSndHrtBtNV12
nciSndHrtBtNV16
nciSndHrtBtNVO3
nciSndHrtBtNVO4

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 73
Obsolete: no
Key: 8030
Inheriting: no


Mandatory Network Variables

nviSpaceTempSpace Temperature Input.:   This input network variable is used to connect an external space temperature sensor to the node. 
Member Number: 1
Base type:
SNVT_temp_p
Direction: input
Service: any
nviSetPointTemperature Setpoint Input.:   This input network variable is used to allow the temperature setpoint for the occupied and standby mode to be changed via the network. 
Member Number: 2
Base type:
SNVT_temp_p
Direction: input
Service: any
nvoSpaceTempSpace Temperature Output.:   This output network variable is used to send the value of the controlled space temperature (either from a locally connected space temperature sensor or from the nviSpaceTemp input) to other nodes.  
Member Number: 3
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoUnitStatusUnit Status Output.:   This output network variable is available to report the object status. 
Member Number: 4
Base type:
SNVT_hvac_status
Direction: output
Service: unacknowledged


Optional Network Variables

nviApplicModeApplication Mode Input.:   This network variable input is used to coordinate the RTU Device with any supervisory controller or intelligent human interface device. 
Member Number: 5
Base type:
SNVT_hvac_mode
Direction: input
Service: any
nviOccCmdOccupancy Input.:   This input network variable is used to command the RTU object into different occupancy modes. It is typically set by a supervisory node. 
Member Number: 6
Base type:
SNVT_occupancy
Direction: input
Service: any
nviSetPtOffsetSetpoint Offset Input.:   This input network variable is used to shift the temperature setpoint via the network by adding nviSetPtOffset to the current setpoint. 
Member Number: 7
Base type:
SNVT_temp_p
Direction: input
Service: any
nviOutsideTempOutside Temperature Input.:   This input network variable is the current outside air temperature. 
Member Number: 8
Base type:
SNVT_temp_p
Direction: input
Service: any
nviOutsideRHOutside Humidity Input.:   This input network variable is the current outside air relative humidity. 
Member Number: 9
Base type:
SNVT_lev_percent
Direction: input
Service: any
nvoEffectSetPtEffective Setpoint Output.:   The output network variable is used to inform the effective setpoint temperature when the setpoint is changed by nciSetPnts, nviSetPoint, nviSetPointOffset or local means.  
Member Number: 10
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoOutsideTempOutside Temperature Output.:   This output network variable is the current outside air temperature. 
Member Number: 11
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoOutsideRHOutside Humidity Output.:   This output network variable is the current outside air relative humidity. 
Member Number: 12
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoCO2CO2 Sensor Output.:   This output network variable is the CO2 measurement. 
Member Number: 16
Base type:
SNVT_ppm
Direction: output
Service: unacknowledged
nviSpaceRHSpace Humidity Input.:   This input network variable measures the space relative humidity. 
Member Number: 13
Base type:
SNVT_lev_percent
Direction: input
Service: any
nviCO2CO2 Sensor Input.:   This input network variable measures the CO2 levels in PPM. 
Member Number: 14
Base type:
SNVT_ppm
Direction: input
Service: any
nviEmergCmdEmergency Command Input.:   This input network variable is used to command the RTU object into different emergency modes. 
Member Number: 15
Base type:
SNVT_hvac_emerg
Direction: input
Service: any


Mandatory Configuration Properties

nciSetPntsOccupancy temperature setpoints.:   The occupancy temperature setpoints for heat and cool mode. 
Member Number: 8
Base type:
SCPTsetPnts
Applies to SFPTroofTopUnit
Array: not permitted
Minimum: -10,00,-10,00,-10,00,-10,00,-10,00,-10,00
Maximum: 35,00,35,00,35,00,35,00,35,00,35,00
Default: 23,00,25,00,28,00,21,00,19,00,16,00
nciSndHrtBtMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 18
Base type:
SCPTmaxSendTime
Applies to SFPTroofTopUnit
Array: not permitted
Default: 0,0


Optional Configuration Properties

nciSndHrtBtNV10Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 3
Base type:
SCPTmaxSendTime
Applies to nvoEffectSetPt
Array: not permitted
Default: 0,0
nciSndHrtBtNV12Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 4
Base type:
SCPTmaxSendTime
Applies to nvoOutsideRH
Array: not permitted
Default: 0,0
nciSndHrtBtNV16Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 5
Base type:
SCPTmaxSendTime
Applies to nviEmergCmd
Array: not permitted
Default: 0,0
nciSndHrtBtNV11Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 7
Base type:
SCPTmaxSendTime
Applies to nvoOutsideTemp
Array: not permitted
Default: 0,0
nciRcvHrtBtNV14Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 9
Base type:
SCPTmaxRcvTime
Applies to nviSpaceRH
Array: not permitted
Default: 0,0
nciRcvHrtBtNV01Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 10
Base type:
SCPTmaxRcvTime
Applies to nviSpaceTemp
Array: not permitted
Default: 0,0
nciRcvHrtBtNV07Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 11
Base type:
SCPTmaxRcvTime
Applies to nviSetPtOffset
Array: not permitted
Default: 0,0
nciRcvHrtBtNV08Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 12
Base type:
SCPTmaxRcvTime
Applies to nviOutsideTemp
Array: not permitted
Default: 0,0
nciRcvHrtBtNV09Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 13
Base type:
SCPTmaxRcvTime
Applies to nviOutsideRH
Array: not permitted
Default: 0,0
nciRcvHrtBtNV05Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 14
Base type:
SCPTmaxRcvTime
Applies to nviApplicMode
Array: not permitted
Default: 0,0
nciRcvHrtBtNV13Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 15
Base type:
SCPTmaxRcvTime
Applies to nvoCO2
Array: not permitted
Default: 0,0
nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 16
Base type:
SCPTlocation
Applies to SFPTroofTopUnit
Array: not permitted
Default: 00*31
nciCO2LimitCO2 limit.:   CO2 threshold limit, controller to maintain concentration below this limit. 
Member Number: 17
Base type:
SCPTlimitCO2
Applies to SFPTroofTopUnit
Array: not permitted
Default: 0
nciSndHrtBtNVO3Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 19
Base type:
SCPTmaxSendTime
Applies to nvoSpaceTemp
Array: not permitted
Default: 0,0
nciSndHrtBtNVO4Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 20
Base type:
SCPTmaxSendTime
Applies to nvoUnitStatus
Array: not permitted
Default: 0,0
nciRcvHrtBtMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 21
Base type:
SCPTmaxRcvTime
Applies to SFPTroofTopUnit
Array: not permitted
Default: 0,0