Single-Phase SubMeter.. The SubMeter is used to provide basic power metering and ON/OFF control of a load
by a remote control of a relay (switch).
|
|
Network Variables | Configuration Properties |
nvoCurrentRms nvoEngyActive nvoLineFrequency nvoPowerFactor nvoVoltageRms
nviEngyActiveSet nviSwitch nvoPowerActive nvoPowerApparent nvoPowerReactive nvoSwitchFb
| cpMinSendTimeCurrentRms cpMinSendTimeEngyActive cpMinSendTimeLineLineFrequency cpMinSendTimePowerFactor cpMinSendTimeVoltageRms
cpDbhSwitchFb cpLocation cpMaxRcvTimeSwitch cpMaxSendTimeCurrentRms cpMaxSendTimeEngyActive cpMaxSendTimeLineFrequency cpMaxSendTimePowerActive cpMaxSendTimePowerApparent cpMaxSendTimePowerFactor cpMaxSendTimePowerReactive cpMaxSendTimeSwitchFb cpMaxSendTimeVoltageRms cpMinSendTimePowerActive cpMinSendTimePowerApparent cpMinSendTimePowerReactive cpObjMajVer cpObjMinVer cpSendOnDeltaCurrentRms cpSendOnDeltaEngyActive cpSendOnDeltaLineFrequency cpSendOnDeltaPowerActive cpSendOnDeltaPowerApparent cpSendOnDeltaPowerFactor cpSendOnDeltaPowerReactive cpSendOnDeltaVoltageRms
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 108 |
Obsolete:
| no |
Key:
| 2161 |
Inheriting:
| no |
Mandatory Network Variables |
nvoEngyActive | Active Energy value output.: This output network variable is used to send the Active Energy value of the Sub Meter.
|
Member Number:
| 1 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoVoltageRms | Voltage RMS value output.: This network variable contains the Instantaneous Voltage RMS Value of the Sub Meter.
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoCurrentRms | Current RMS value output.: This network variable contains the Instantaneous Current RMS Value of the Sub Meter.
|
Member Number:
| 3 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoPowerFactor | Power Factor value output.: This network variable contains the Instantaneous Power Factor Value of the Sub Meter.
|
Member Number:
| 4 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoLineFrequency | Line Frequency value output.: This network variable contains the Instantaneous Line Frequency Value of the Sub Meter.
|
Member Number:
| 5 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
Optional Network Variables |
nvoPowerActive | Active Power value output.: This network variable contains the Instantaneous Active Power Value of the SubMeter.
|
Member Number:
| 6 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoPowerReactive | Reactive Power value output.: This network variable contains the Instantaneous Reactive Power Value of the SubMeter.
|
Member Number:
| 7 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoPowerApparent | Apparent Power value output.: This network variable contains the Instantaneous Apparent Power Value of the SubMeter.
|
Member Number:
| 8 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nviEngyActiveSet | Set and Reset Active Energy value input.: This network variable contains the input value of the nviEngyActiveSet.
|
Member Number:
| 9 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoSwitchFb | Switch Feedback output.: This output network variable provides the state of the switch actuator (ON or OFF)
|
Member Number:
| 10 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nviSwitch | Switch State input.: This input network variable provides a way for another device to pass switch value to the switch actuator.
|
Member Number:
| 11 |
Base type:
| | Direction:
| input | Service:
| any |
|
Mandatory Configuration Properties |
cpMinSendTimeEngyActive | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
Member Number:
| 1 |
Base type:
| |
Applies to
| nvoEngyActive | Array:
| not permitted | Default:
| 10,0 |
|
cpMinSendTimeVoltageRms | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
Member Number:
| 2 |
Base type:
| |
Applies to
| nvoVoltageRms | Array:
| not permitted | Default:
| 30,0 |
|
cpMinSendTimeCurrentRms | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
Member Number:
| 3 |
Base type:
| |
Applies to
| nvoCurrentRms | Array:
| not permitted | Default:
| 30,0 |
|
cpMinSendTimePowerFactor | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
Member Number:
| 4 |
Base type:
| |
Applies to
| nvoPowerFactor | Array:
| not permitted | Default:
| 30,0 |
|
cpMinSendTimeLineLineFrequency | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
Member Number:
| 5 |
Base type:
| |
Applies to
| nvoLineFrequency | Array:
| not permitted | Default:
| 30,0 |
|
Optional Configuration Properties |
cpMinSendTimePowerActive | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
Member Number:
| 6 |
Base type:
| |
Applies to
| nvoPowerActive | Array:
| not permitted | Default:
| 30,0 |
|
cpMinSendTimePowerReactive | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
Member Number:
| 7 |
Base type:
| |
Applies to
| nvoPowerReactive | Array:
| not permitted | Default:
| 30,0 |
|
cpMinSendTimePowerApparent | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
Member Number:
| 8 |
Base type:
| |
Applies to
| nvoPowerApparent | Array:
| not permitted | Default:
| 30,0 |
|
cpMaxSendTimeEngyActive | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 9 |
Base type:
| |
Applies to
| nvoEngyActive | Array:
| not permitted | Default:
| 300,0 |
|
cpMaxSendTimeVoltageRms | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 10 |
Base type:
| |
Applies to
| nvoVoltageRms | Array:
| not permitted | Default:
| 0,0 |
|
cpMaxSendTimeCurrentRms | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 11 |
Base type:
| |
Applies to
| nvoCurrentRms | Array:
| not permitted | Default:
| 0,0 |
|
cpMaxSendTimePowerFactor | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 12 |
Base type:
| |
Applies to
| nvoPowerFactor | Array:
| not permitted | Default:
| 0,0 |
|
cpMaxSendTimeLineFrequency | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 13 |
Base type:
| |
Applies to
| nvoLineFrequency | Array:
| not permitted | Default:
| 0,0 |
|
cpMaxSendTimePowerActive | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 14 |
Base type:
| |
Applies to
| nvoPowerActive | Array:
| not permitted | Default:
| 0,0 |
|
cpMaxSendTimePowerReactive | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 15 |
Base type:
| |
Applies to
| nvoPowerReactive | Array:
| not permitted | Default:
| 0,0 |
|
cpMaxSendTimePowerApparent | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 16 |
Base type:
| |
Applies to
| nvoPowerApparent | Array:
| not permitted | Default:
| 0,0 |
|
cpSendOnDeltaEngyActive | Send on delta.: The minimum change required to force transmission of the output value.
|
Member Number:
| 18 |
Base type:
| |
Applies to
| nvoEngyActive | Array:
| not permitted | Default:
| 1,0 |
|
cpSendOnDeltaVoltageRms | Send on delta.: The minimum change required to force transmission of the output value.
|
Member Number:
| 19 |
Base type:
| |
Applies to
| nvoVoltageRms | Array:
| not permitted | Default:
| 5,0 |
|
cpSendOnDeltaCurrentRms | Send on delta.: The minimum change required to force transmission of the output value.
|
Member Number:
| 20 |
Base type:
| |
Applies to
| nvoCurrentRms | Array:
| not permitted | Default:
| 5,0 |
|
cpSendOnDeltaPowerFactor | Send on delta.: The minimum change required to force transmission of the output value.
|
Member Number:
| 21 |
Base type:
| |
Applies to
| nvoPowerFactor | Array:
| not permitted | Default:
| 5,0 |
|
cpSendOnDeltaLineFrequency | Send on delta.: The minimum change required to force transmission of the output value.
|
Member Number:
| 22 |
Base type:
| |
Applies to
| nvoLineFrequency | Array:
| not permitted | Default:
| 5,0 |
|
cpSendOnDeltaPowerActive | Send on delta.: The minimum change required to force transmission of the output value.
|
Member Number:
| 23 |
Base type:
| |
Applies to
| nvoPowerActive | Array:
| not permitted | Default:
| 1,0 |
|
cpSendOnDeltaPowerReactive | Send on delta.: The minimum change required to force transmission of the output value.
|
Member Number:
| 24 |
Base type:
| |
Applies to
| nvoPowerReactive | Array:
| not permitted | Default:
| 1,0 |
|
cpSendOnDeltaPowerApparent | Send on delta.: The minimum change required to force transmission of the output value.
|
Member Number:
| 25 |
Base type:
| |
Applies to
| nvoPowerApparent | Array:
| not permitted | Default:
| 1,0 |
|
cpObjMajVer | Object major version number.: The major version number for the object.
|
|
cpObjMinVer | Object minor version number.: The minor version number for the object.
|
|
cpLocation | Location: Provides descriptive physical location information related to the object.
|
|
cpMaxSendTimeSwitchFb | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 31 |
Base type:
| |
Applies to
| nvoSwitchFb | Array:
| not permitted | Default:
| 300,0 |
|
cpMaxRcvTimeSwitch | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 32 |
Base type:
| |
Applies to
| nviSwitch | Array:
| not permitted | Default:
| 600,0 |
|
cpDbhSwitchFb | Default behavior.: Selects which set of values will be used on power-up and communication failure, between the stated default values (0), or manufacturer-specified values (1)
|
Member Number:
| 33 |
Base type:
| |
Applies to
| nvoSwitchFb | Array:
| not permitted | Default:
| 100,0 1 |
|