Smoke (Intelligent) Fire Initiator.. Intelligent (addressable) Smoke Fire Initiator object for fire-alarm notification and response functions.
|
|
Network Variables | Configuration Properties |
nviDeviceRequest nvoFireAlm nvoFireTrouble
nvoDayNightMode nvoEmergMode nvoEnvComp
| nciDayAlarm nciDayPreAlarm nciMaxSendTime nciNightAlarm nciNightPreAlarm nciNodeLocation nciNomSens nciZoneNum
nciFireText1 nciFireText2 nciFireText3 nciInstallDate nciMaintDate nciManufDate nciOEMLabel
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 38 |
Obsolete:
| no |
Key:
| 11002 |
Inheriting:
| no |
Mandatory Network Variables |
nvoFireAlm | Fire alarm.: Fire information for use by simple indicators.
|
Member Number:
| 1 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoFireTrouble | Fire trouble.: Initiator trouble information for use by simple indicators.
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| any |
|
nviDeviceRequest | Device request.: Receives requests intended to perform smoke detector operations, initiated from operator.
|
Member Number:
| 3 |
Base type:
| | Direction:
| input | Service:
| any |
|
Optional Network Variables |
nvoDayNightMode | Day (0%; 0) and Night (100%; 1) mode.: Present value for Day/Night mode. The DayNightMode variable is used by applications that use day/night -sensitive limits depending upon time of day.
|
Member Number:
| 4 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoEnvComp | Environmental compensation.: For use by operator-interface devices requiring system, environmental-compensation reporting.
|
Member Number:
| 5 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoEmergMode | Emergency mode: EMERG_NORMAL or EMERG_FIRE.: Controls the (actuator) position for smoke-control devices.
|
Member Number:
| 6 |
Base type:
| | Direction:
| output | Service:
| any | Minimum:
| EMERG_NORMAL | Maximum:
| EMERG_FIRE |
|
Mandatory Configuration Properties |
nciNodeLocation | Location: Provides descriptive physical location information related to the object.
|
|
nciMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 2 |
Base type:
| |
Applies to
| nvoFireAlm | Array:
| not permitted |
|
nciNomSens | Nominal sensitivity.: The nominal sensitivity value for the fire initiator in percentage obscuration by smoke.
|
|
nciDayAlarm | Daytime alarm limit.: The daytime alarm limit sensitivity value for the fire initiator in percentage obscuration by smoke.
|
|
nciNightAlarm | Nighttime alarm limit.: The nighttime alarm limit sensitivity value for the fire initiator in percentage obscuration by smoke.
|
|
nciDayPreAlarm | Daytime pre-alarm limit.: The daytime pre-alarm limit sensitivity value for the fire initiator in percentage obscuration by smoke.
|
|
nciNightPreAlarm | Nighttime pre-alarm limit.: The nighttime pre-alarm limit sensitivity value for the fire initiator in percentage obscuration by smoke.
|
|
nciZoneNum | Zone number.: The zone number for the device.
|
|
Optional Configuration Properties |
nciOEMLabel | OEM label.: The label, programmed by the OEM, to identify the unit name.
|
|
nciInstallDate | Installation date.: The date of installation for the device.
|
|
nciMaintDate | Maintenance date.: The date of last maintenance for the device.
|
|
nciManufDate | Manufacture date.: The date of manufacture for the device.
|
|
nciFireText1 | Fire text information.: Text information relevant to fire conditions. A '>' at end of string indicates presence of fire text 2.
|
|
nciFireText2 | Fire text information, continuation.: Continuation text information relevant to fire conditions. A '>' at end of string indicates presence of fire text 3.
|
|
nciFireText3 | Fire text information, second continuation.: Second continuation text information relevant to fire conditions.
|
|