Universal Fire Indicator.. Generic indicator of the presence of fire by manufacturer-defined means.
|
|
Network Variables | Configuration Properties |
nviUFIState
nvoFireTrouble
| nciIndicator nciLocation nciMaxReceiveT nciZoneNumber
nciFireText1 nciFireText2 nciFireText3 nciInstallDate nciMaintDate nciManfDate nciOEMLable
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 58 |
Obsolete:
| no |
Key:
| 11011 |
Inheriting:
| no |
Principal Variable
| nviUFIState |
Mandatory Network Variables |
nviUFIState | Universal Fire Indicator State.: The input NV controls the indicator device.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
Optional Network Variables |
nvoFireTrouble | Indicator Trouble.: This output NV reflects the operational condition of the indicator device.
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
Mandatory Configuration Properties |
nciIndicator | Fire indicator device type.: Describes the fire indicator device.
|
|
nciLocation | Location: Provides descriptive physical location information related to the object.
|
|
nciMaxReceiveT | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
|
nciZoneNumber | Zone number.: The zone number for the device.
|
|
Optional Configuration Properties |
nciFireText1 | Fire text information.: Text information relevant to fire conditions. A '>' at end of string indicates presence of fire text 2.
|
Member Number:
| 5 |
Base type:
| |
Applies to
| SFPTuniversalFireIndicator | Flags:
| modify when disabled | Array:
| not permitted | Minimum:
| 00*31 | Maximum:
| FF*30-00 | Default:
| 00*31 |
|
nciFireText2 | Fire text information, continuation.: Continuation text information relevant to fire conditions. A '>' at end of string indicates presence of fire text 3.
|
Member Number:
| 6 |
Base type:
| |
Applies to
| SFPTuniversalFireIndicator | Flags:
| modify when disabled | Array:
| not permitted | Minimum:
| 00*31 | Maximum:
| FF*30-00 | Default:
| 00*31 |
|
nciFireText3 | Fire text information, second continuation.: Second continuation text information relevant to fire conditions.
|
Member Number:
| 7 |
Base type:
| |
Applies to
| SFPTuniversalFireIndicator | Flags:
| modify when disabled | Array:
| not permitted | Minimum:
| 00*31 | Maximum:
| FF*30-00 | Default:
| 00*31 |
|
nciInstallDate | Installation date.: The date of installation for the device.
|
|
nciMaintDate | Maintenance date.: The date of last maintenance for the device.
|
|
nciManfDate | Manufacture date.: The date of manufacture for the device.
|
Member Number:
| 10 |
Base type:
| |
Applies to
| SFPTuniversalFireIndicator | Flags:
| manufacturer specific, constant | Array:
| not permitted | Default:
| 0/0/0 0:0:0 |
|
nciOEMLable | OEM label.: The label, programmed by the OEM, to identify the unit name.
|
Member Number:
| 11 |
Base type:
| |
Applies to
| SFPTuniversalFireIndicator | Flags:
| manufacturer specific, constant | Array:
| not permitted | Minimum:
| 00*31 | Maximum:
| FF*16-00*15 | Default:
| 00*31 |
|