Utility Meter.. To register measuring information from utility meters for remote metering.
|
|
Network Variables | Configuration Properties |
nviHistTime nvoHistVal nvoMeterVal
| nciHistPeriod nciSendOnDelta
nciLocation nciNumDigits nciObjMajVer nciObjMinVer nciPulseConst nciStartVal
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 80 |
Obsolete:
| no |
Key:
| 2201 |
Inheriting:
| no |
Mandatory Network Variables |
nvoMeterVal | Meter Value Output.: This network variable contains the present value of the meter, i.e., the actual running value hown by the display on the meter.
|
Member Number:
| 1 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoHistVal | Historical Value Output.: This network variable contains, by default, a copy of the valid meter value at the turn of the last month.
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nviHistTime | Historical-Time Selection Input.: This input network variable controls which history value is shown on the output network variable: nvoHistVal.
|
Member Number:
| 3 |
Base type:
| | Direction:
| input | Service:
| any |
|
Mandatory Configuration Properties |
nciSendOnDelta | Send on delta.: The minimum change required to force transmission of the output value.
|
Member Number:
| 1 |
Base type:
| |
Applies to
| nvoMeterVal | Array:
| not permitted | Default:
| 00*4 |
|
nciHistPeriod | Historical Period.: This input configuration network variable defines the period of time between transfer of a values to the historical register.
|
Member Number:
| 2 |
Base type:
| |
Applies to
| nvoHistVal | Array:
| not permitted | Default:
| IOM_MINUTE 0 |
|
Optional Configuration Properties |
nciLocation | Location: Provides descriptive physical location information related to the object.
|
Member Number:
| 3 |
Base type:
| |
Applies to
| SFPTutilityMeter | Array:
| not permitted | Default:
| 00*31 |
|
nciStartVal | Base value.: The base value (where to begin counting)
|
Member Number:
| 4 |
Base type:
| |
Applies to
| SFPTutilityMeter | Flags:
| modify when disabled | Array:
| not permitted | Default:
| 0 RVU_NONE 0 |
|
nciPulseConst | Pulse and Transformer Constant.: This configuration property is used to scale the raw pulse value to an energy-meter value.
|
Member Number:
| 5 |
Base type:
| |
Applies to
| SFPTutilityMeter | Flags:
| modify when disabled | Array:
| not permitted | Default:
| 0 0 |
|
nciNumDigits | Number of Digits on the Meter.: This configuration property is used for setting the total number of digits on the meter.
|
Member Number:
| 6 |
Base type:
| |
Applies to
| SFPTutilityMeter | Flags:
| modify when disabled | Array:
| not permitted | Default:
| 0 |
|
nciObjMajVer | Object major version number.: The major version number for the object.
|
Member Number:
| 7 |
Base type:
| |
Applies to
| SFPTutilityMeter | Flags:
| constant | Array:
| not permitted | Default:
| 1 |
|
nciObjMinVer | Object minor version number.: The minor version number for the object.
|
Member Number:
| 8 |
Base type:
| |
Applies to
| SFPTutilityMeter | Flags:
| device specific, constant | Array:
| not permitted | Default:
| 0 |
|