SFPTutilityMeter

Utility Meter..  To register measuring information from utility meters for remote metering. 
 

Network Variables

Configuration Properties

nviHistTime
nvoHistVal
nvoMeterVal

nciHistPeriod
nciSendOnDelta

nciLocation
nciNumDigits
nciObjMajVer
nciObjMinVer
nciPulseConst
nciStartVal

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 80
Obsolete: no
Key: 2201
Inheriting: no


Mandatory Network Variables

nvoMeterValMeter Value Output.:   This network variable contains the present value of the meter, i.e., the actual running value hown by the display on the meter. 
Member Number: 1
Base type:
SNVT_reg_val_ts
Direction: output
Service: acknowledged
nvoHistValHistorical Value Output.:   This network variable contains, by default, a copy of the valid meter value at the turn of the last month. 
Member Number: 2
Base type:
SNVT_reg_val_ts
Direction: output
Service: acknowledged
nviHistTimeHistorical-Time Selection Input.:   This input network variable controls which history value is shown on the output network variable: nvoHistVal. 
Member Number: 3
Base type:
SNVT_time_stamp
Direction: input
Service: any


Mandatory Configuration Properties

nciSendOnDeltaSend on delta.:   The minimum change required to force transmission of the output value. 
Member Number: 1
Base type:
SCPTsndDelta
Applies to nvoMeterVal
Array: not permitted
Default: 00*4
nciHistPeriodHistorical Period.:   This input configuration network variable defines the period of time between transfer of a values to the historical register. 
Member Number: 2
Base type:
SCPTtimePeriod
Applies to nvoHistVal
Array: not permitted
Default: IOM_MINUTE 0


Optional Configuration Properties

nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 3
Base type:
SCPTlocation
Applies to SFPTutilityMeter
Array: not permitted
Default: 00*31
nciStartValBase value.:   The base value (where to begin counting) 
Member Number: 4
Base type:
SCPTbaseValue
Applies to SFPTutilityMeter
Flags: modify when disabled
Array: not permitted
Default: 0 RVU_NONE 0
nciPulseConstPulse and Transformer Constant.:   This configuration property is used to scale the raw pulse value to an energy-meter value. 
Member Number: 5
Base type:
SCPTpulseValue
Applies to SFPTutilityMeter
Flags: modify when disabled
Array: not permitted
Default: 0 0
nciNumDigitsNumber of Digits on the Meter.:   This configuration property is used for setting the total number of digits on the meter. 
Member Number: 6
Base type:
SCPTnumDigits
Applies to SFPTutilityMeter
Flags: modify when disabled
Array: not permitted
Default: 0
nciObjMajVerObject major version number.:   The major version number for the object. 
Member Number: 7
Base type:
SCPTobjMajVer
Applies to SFPTutilityMeter
Flags: constant
Array: not permitted
Default: 1
nciObjMinVerObject minor version number.:   The minor version number for the object. 
Member Number: 8
Base type:
SCPTobjMinVer
Applies to SFPTutilityMeter
Flags: device specific, constant
Array: not permitted
Default: 0