Thermostat. Use to adjust HVAC setpoints for one or more heating/cooling units, and act upon temperature inputs for automated loop control.
|
| |
Network Variables | Configuration Properties |
nviSetPoint nvoCoolOutput nvoHeatOutput nvoSpaceTemp nvoUnitStatus
nviApplicMode nviEnergyHoldOff nviOccCmd nviSetPtOffset nviSpaceTemp nvoEffectSetPt nvoEnergyHoldOff nvoTerminalFan nvoTerminalLoad
| nciSetPnts nciSndHrtBt
nciLocation nciLrSPCool nciLrSPHeat nciMinDelta nciRcvHrtBt nciRcvHrtBtNV06 nciRcvHrtBtNV08 nciRcvHrtBtNV09 nciRcvHrtBtNV10 nciSndHrtBtNV02 nciSndHrtBtNV03 nciSndHrtBtNV04 nciSndHrtBtNV05 nciSndHrtBtNV12 nciSndHrtBtNV14 nciUpSPCool nciUpSPHeat
|
| |
Details: |
| Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
| Index:
| 74 |
| Obsolete:
| no |
| Key:
| 8060 |
|
Inheriting:
| no |
Mandatory Network Variables |
| nviSetPoint | Temperature Setpoint Input.: This input network variable is used to allow the temperature setpoint for the occupied and standby mode being changed via the network.
|
| Member Number:
| 1 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nvoHeatOutput | Heat Control Output.: This output network variable reflects the current position of the heat actuator and can be used as part of a control loop and for monitoring purposes.
|
| Member Number:
| 2 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
| nvoCoolOutput | Cool Control Output.: This output network variable reflects the current position of the cool actuator and can be used as part of a control loop and for monitoring purposes.
|
| Member Number:
| 3 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
| nvoSpaceTemp | Space Temperature Output.: This output network variable is used to send the value of a locally connected space temperature sensor to other nodes. It is mandatory to the profile.
|
| Member Number:
| 4 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
| nvoUnitStatus | Unit Status Output.: This output network variable is available to report the object status.
|
| Member Number:
| 5 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
Optional Network Variables |
| nviSpaceTemp | Space Temperature Input.: This input network variable is used to connect an external space temperature sensor to the node.
|
| Member Number:
| 6 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nviOccCmd | Occupancy Input.: This input network variable is used to command the thermostat object into different occupancy modes.
|
| Member Number:
| 7 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nviApplicMode | Application Mode Input.: This network variable input is used to coordinate the thermostat object with any supervisory controller providing the supply energy, e.g. hot or cold water.
|
| Member Number:
| 8 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nviSetPtOffset | Setpoint Offset Input.: This input network variable is used to shift the temperature setpoint via network by adding nviSetPtOffset to the current setpoint.
|
| Member Number:
| 9 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nviEnergyHoldOff | Energy Hold Off Input.: This input is from a device such as a door/window contact sensor.
|
| Member Number:
| 10 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nvoTerminalLoad | Terminal Load Output.: This output network variable reflects the current heat/cool energy demand of the Thermostat Device which is typically bound to an energy providing node.
|
| Member Number:
| 11 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
| nvoEffectSetPt | Effective Setpoint Output.:
The output network variable is used to report the effective setpoint temperature when the setpoint is changed through nciSetPnts, nviSetPoint, nviSetPtOffset or by local means.
|
| Member Number:
| 12 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
| nvoTerminalFan | Terminal Fan.:
This output network variable reflects the current fan speed of a multi-speed (n-speed) fan. It can be used as part of a control loop and for monitoring purposes.
|
| Member Number:
| 13 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
| nvoEnergyHoldOff | Energy Hold Off Output.: This output is used to convey to other devices the state of an EnergyHoldOff device that is hardwired to the controller. Refer to EnergyHoldOff Input.
|
| Member Number:
| 14 | |
Base type:
| | | Direction:
| output | | Service:
| unacknowledged |
|
Mandatory Configuration Properties |
| nciSetPnts | Occupancy temperature setpoints.: The occupancy temperature setpoints for heat and cool mode.
|
| Member Number:
| 5 | |
Base type:
| | |
Applies to
| SFPTthermostat | | Array:
| not permitted | | Minimum:
| -10,00,-10,00,-10,00,-10,00,-10,00,-10,00 | | Maximum:
| 35,00,35,00,35,00,35,00,35,00,35,00 | | Default:
| 23,00,25,00,28,00,21,00,19,00,16,00 |
|
| nciSndHrtBt | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
| Member Number:
| 16 | |
Base type:
| | |
Applies to
| SFPTthermostat | | Array:
| not permitted | | Default:
| 0,0 |
|
Optional Configuration Properties |
| nciRcvHrtBtNV06 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
| Member Number:
| 6 | |
Base type:
| | |
Applies to
| nviSpaceTemp | | Array:
| not permitted | | Default:
| 0,0 |
|
| nciRcvHrtBtNV08 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
| Member Number:
| 7 | |
Base type:
| | |
Applies to
| nviApplicMode | | Array:
| not permitted | | Default:
| 0,0 |
|
| nciRcvHrtBtNV09 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
| Member Number:
| 8 | |
Base type:
| | |
Applies to
| nviSetPtOffset | | Array:
| not permitted | | Default:
| 0,0 |
|
| nciRcvHrtBtNV10 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
| Member Number:
| 9 | |
Base type:
| | |
Applies to
| nviEnergyHoldOff | | Array:
| not permitted | | Default:
| 0,0 |
|
| nciMinDelta | Minimum delta temperature.: The minimum change in temperature required to be treated as significant.
|
| Member Number:
| 10 | |
Base type:
| | |
Applies to
| SFPTthermostat | | Array:
| not permitted | | Minimum:
| 0,00 | | Default:
| 0,00 |
|
| nciLocation | Location: Provides descriptive physical location information related to the object.
|
| Member Number:
| 11 | |
Base type:
| | |
Applies to
| SFPTthermostat | | Array:
| not permitted | | Default:
| 00*31 |
|
| nciUpSPHeat | Heating setpoint upper limit.: Limits the upper extent of the permitted range for the heating setpoint.
|
| Member Number:
| 12 | |
Base type:
| | |
Applies to
| SFPTthermostat | | Array:
| not permitted | | Minimum:
| 10,00 | | Maximum:
| 35,00 | | Default:
| 35,00 |
|
| nciLrSPHeat | Heating setpoint lower limit.: Limits the lower extent of the permitted range for the heating setpoint.
|
| Member Number:
| 13 | |
Base type:
| | |
Applies to
| SFPTthermostat | | Array:
| not permitted | | Minimum:
| 10,00 | | Maximum:
| 35,00 | | Default:
| 10,00 |
|
| nciUpSPCool | Cooling setpoint upper limit.: Limits the upper extent of the permitted range for the cooling setpoint.
|
| Member Number:
| 14 | |
Base type:
| | |
Applies to
| SFPTthermostat | | Array:
| not permitted | | Minimum:
| 10,00 | | Maximum:
| 35,00 | | Default:
| 10,00 |
|
| nciLrSPCool | Cooling setpoint lower limit.: Limits the lower extent of the permitted range for the cooling setpoint.
|
| Member Number:
| 15 | |
Base type:
| | |
Applies to
| SFPTthermostat | | Array:
| not permitted | | Minimum:
| 10,00 | | Maximum:
| 35,00 | | Default:
| 10,00 |
|
| nciSndHrtBtNV02 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
| Member Number:
| 17 | |
Base type:
| | |
Applies to
| nvoHeatOutput | | Array:
| not permitted | | Default:
| 0,0 |
|
| nciSndHrtBtNV03 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
| Member Number:
| 18 | |
Base type:
| | |
Applies to
| nvoCoolOutput | | Array:
| not permitted | | Default:
| 0,0 |
|
| nciSndHrtBtNV04 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
| Member Number:
| 19 | |
Base type:
| | |
Applies to
| nvoSpaceTemp | | Array:
| not permitted | | Default:
| 0,0 |
|
| nciSndHrtBtNV05 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
| Member Number:
| 20 | |
Base type:
| | |
Applies to
| nvoUnitStatus | | Array:
| not permitted | | Default:
| 0,0 |
|
| nciRcvHrtBt | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
| Member Number:
| 21 | |
Base type:
| | |
Applies to
| SFPTthermostat | | Array:
| not permitted | | Default:
| 0,0 |
|
| nciSndHrtBtNV14 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
| Member Number:
| 22 | |
Base type:
| | |
Applies to
| nvoEnergyHoldOff | | Array:
| not permitted | | Default:
| 0,0 |
|
| nciSndHrtBtNV12 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
| Member Number:
| 23 | |
Base type:
| | |
Applies to
| nvoEffectSetPt | | Array:
| not permitted | | Default:
| 0,0 |
|