Thermostat. Use to adjust HVAC setpoints for one or more heating/cooling units, and act upon temperature inputs for automated loop control.
|
|
Network Variables | Configuration Properties |
nviSetPoint nvoCoolOutput nvoHeatOutput nvoSpaceTemp nvoUnitStatus
nviApplicMode nviEnergyHoldOff nviOccCmd nviSetPtOffset nviSpaceTemp nvoEffectSetPt nvoEnergyHoldOff nvoTerminalFan nvoTerminalLoad
| nciSetPnts nciSndHrtBt
nciLocation nciLrSPCool nciLrSPHeat nciMinDelta nciRcvHrtBt nciRcvHrtBtNV06 nciRcvHrtBtNV08 nciRcvHrtBtNV09 nciRcvHrtBtNV10 nciSndHrtBtNV02 nciSndHrtBtNV03 nciSndHrtBtNV04 nciSndHrtBtNV05 nciSndHrtBtNV12 nciSndHrtBtNV14 nciUpSPCool nciUpSPHeat
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 74 |
Obsolete:
| no |
Key:
| 8060 |
Inheriting:
| no |
Mandatory Network Variables |
nviSetPoint | Temperature Setpoint Input.: This input network variable is used to allow the temperature setpoint for the occupied and standby mode being changed via the network.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoHeatOutput | Heat Control Output.: This output network variable reflects the current position of the heat actuator and can be used as part of a control loop and for monitoring purposes.
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoCoolOutput | Cool Control Output.: This output network variable reflects the current position of the cool actuator and can be used as part of a control loop and for monitoring purposes.
|
Member Number:
| 3 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoSpaceTemp | Space Temperature Output.: This output network variable is used to send the value of a locally connected space temperature sensor to other nodes. It is mandatory to the profile.
|
Member Number:
| 4 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoUnitStatus | Unit Status Output.: This output network variable is available to report the object status.
|
Member Number:
| 5 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
Optional Network Variables |
nviSpaceTemp | Space Temperature Input.: This input network variable is used to connect an external space temperature sensor to the node.
|
Member Number:
| 6 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviOccCmd | Occupancy Input.: This input network variable is used to command the thermostat object into different occupancy modes.
|
Member Number:
| 7 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviApplicMode | Application Mode Input.: This network variable input is used to coordinate the thermostat object with any supervisory controller providing the supply energy, e.g. hot or cold water.
|
Member Number:
| 8 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviSetPtOffset | Setpoint Offset Input.: This input network variable is used to shift the temperature setpoint via network by adding nviSetPtOffset to the current setpoint.
|
Member Number:
| 9 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviEnergyHoldOff | Energy Hold Off Input.: This input is from a device such as a door/window contact sensor.
|
Member Number:
| 10 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoTerminalLoad | Terminal Load Output.: This output network variable reflects the current heat/cool energy demand of the Thermostat Device which is typically bound to an energy providing node.
|
Member Number:
| 11 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoEffectSetPt | Effective Setpoint Output.:
The output network variable is used to report the effective setpoint temperature when the setpoint is changed through nciSetPnts, nviSetPoint, nviSetPtOffset or by local means.
|
Member Number:
| 12 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoTerminalFan | Terminal Fan.:
This output network variable reflects the current fan speed of a multi-speed (n-speed) fan. It can be used as part of a control loop and for monitoring purposes.
|
Member Number:
| 13 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoEnergyHoldOff | Energy Hold Off Output.: This output is used to convey to other devices the state of an EnergyHoldOff device that is hardwired to the controller. Refer to EnergyHoldOff Input.
|
Member Number:
| 14 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
Mandatory Configuration Properties |
nciSetPnts | Occupancy temperature setpoints.: The occupancy temperature setpoints for heat and cool mode.
|
Member Number:
| 5 |
Base type:
| |
Applies to
| SFPTthermostat | Array:
| not permitted | Minimum:
| -10,00,-10,00,-10,00,-10,00,-10,00,-10,00 | Maximum:
| 35,00,35,00,35,00,35,00,35,00,35,00 | Default:
| 23,00,25,00,28,00,21,00,19,00,16,00 |
|
nciSndHrtBt | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 16 |
Base type:
| |
Applies to
| SFPTthermostat | Array:
| not permitted | Default:
| 0,0 |
|
Optional Configuration Properties |
nciRcvHrtBtNV06 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 6 |
Base type:
| |
Applies to
| nviSpaceTemp | Array:
| not permitted | Default:
| 0,0 |
|
nciRcvHrtBtNV08 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 7 |
Base type:
| |
Applies to
| nviApplicMode | Array:
| not permitted | Default:
| 0,0 |
|
nciRcvHrtBtNV09 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 8 |
Base type:
| |
Applies to
| nviSetPtOffset | Array:
| not permitted | Default:
| 0,0 |
|
nciRcvHrtBtNV10 | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 9 |
Base type:
| |
Applies to
| nviEnergyHoldOff | Array:
| not permitted | Default:
| 0,0 |
|
nciMinDelta | Minimum delta temperature.: The minimum change in temperature required to be treated as significant.
|
Member Number:
| 10 |
Base type:
| |
Applies to
| SFPTthermostat | Array:
| not permitted | Minimum:
| 0,00 | Default:
| 0,00 |
|
nciLocation | Location: Provides descriptive physical location information related to the object.
|
Member Number:
| 11 |
Base type:
| |
Applies to
| SFPTthermostat | Array:
| not permitted | Default:
| 00*31 |
|
nciUpSPHeat | Heating setpoint upper limit.: Limits the upper extent of the permitted range for the heating setpoint.
|
Member Number:
| 12 |
Base type:
| |
Applies to
| SFPTthermostat | Array:
| not permitted | Minimum:
| 10,00 | Maximum:
| 35,00 | Default:
| 35,00 |
|
nciLrSPHeat | Heating setpoint lower limit.: Limits the lower extent of the permitted range for the heating setpoint.
|
Member Number:
| 13 |
Base type:
| |
Applies to
| SFPTthermostat | Array:
| not permitted | Minimum:
| 10,00 | Maximum:
| 35,00 | Default:
| 10,00 |
|
nciUpSPCool | Cooling setpoint upper limit.: Limits the upper extent of the permitted range for the cooling setpoint.
|
Member Number:
| 14 |
Base type:
| |
Applies to
| SFPTthermostat | Array:
| not permitted | Minimum:
| 10,00 | Maximum:
| 35,00 | Default:
| 10,00 |
|
nciLrSPCool | Cooling setpoint lower limit.: Limits the lower extent of the permitted range for the cooling setpoint.
|
Member Number:
| 15 |
Base type:
| |
Applies to
| SFPTthermostat | Array:
| not permitted | Minimum:
| 10,00 | Maximum:
| 35,00 | Default:
| 10,00 |
|
nciSndHrtBtNV02 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 17 |
Base type:
| |
Applies to
| nvoHeatOutput | Array:
| not permitted | Default:
| 0,0 |
|
nciSndHrtBtNV03 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 18 |
Base type:
| |
Applies to
| nvoCoolOutput | Array:
| not permitted | Default:
| 0,0 |
|
nciSndHrtBtNV04 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 19 |
Base type:
| |
Applies to
| nvoSpaceTemp | Array:
| not permitted | Default:
| 0,0 |
|
nciSndHrtBtNV05 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 20 |
Base type:
| |
Applies to
| nvoUnitStatus | Array:
| not permitted | Default:
| 0,0 |
|
nciRcvHrtBt | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 21 |
Base type:
| |
Applies to
| SFPTthermostat | Array:
| not permitted | Default:
| 0,0 |
|
nciSndHrtBtNV14 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 22 |
Base type:
| |
Applies to
| nvoEnergyHoldOff | Array:
| not permitted | Default:
| 0,0 |
|
nciSndHrtBtNV12 | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 23 |
Base type:
| |
Applies to
| nvoEffectSetPt | Array:
| not permitted | Default:
| 0,0 |
|