Discharge-Air Controller (DAC). Used to control duct static pressure and discharge-air temperature.
|
|
Network Variables | Configuration Properties |
nviOccSchedule nvoDischAirTemp nvoUnitStatus
nviApplicMode nviBldgStatPress nviBldgStaticSP nviCWFlow nviCWTemp nviDAClSP nviDADewPointSP nviDAHtSP nviDehumEnable nviDuctStatPress nviDuctStaticSP nviEconEnable nviEmergOverride nviExhFanCap nviFanDiffSP nviHumEnable nviMATSP nviMinOAFlowSP nviOAEnthalpy nviOAMinPos nviOccManCmd nviOutdoorRH nviOutdoorTemp nviPriCoolEnable nviPriHeatEnable nviRATemp nviRetFanCap nviSpaceDehumSP nviSpaceEnthalpy nviSpaceHumSP nviSpaceRH nviSpaceTemp nviSupFanCap nvoApplicMode nvoBldgStatPress nvoCWFlow nvoCWPump nvoCWTemp nvoCondCap nvoCoolPrimary nvoDADewPoint nvoDehumidifier nvoDuctStatPress nvoEconEnabled nvoEffDADewPtSP nvoEffDATempSP nvoEffDuctStatSP nvoEffSpaceDHSP nvoEffSpaceHumSP nvoEffectOccup nvoExhDamper nvoExhFanCap nvoExhFanOnOff nvoExhFanStatus nvoHeatCool nvoHeatPrimary nvoHumidifier nvoLocalCWTemp nvoLocalOARH nvoLocalOATemp nvoMATemp nvoOADamper nvoOAEnthalpy nvoOAFlow nvoOutdoorRH nvoOutdoorTemp nvoRATemp nvoRetFanCap nvoRetFanOnOff nvoRetFanPress nvoRetFanStatus nvoSpaceEnthalpy nvoSpaceRH nvoSpaceTemp nvoSupFanCap nvoSupFanOnOff nvoSupFanStatus
| nciDAClSP nciDAHtSP nciSndHrtBt
nciBldgStaticSP nciBypassTime nciCoolLockout nciCoolResetEn nciDADewPointSP nciDuctStatLim nciDuctStatSP nciExhStartPos nciFanDiffSP nciHeatLockout nciHeatResetEn nciLocation nciMALowLimitSP nciMATSP nciMaxDAClSP nciMaxDAHtSP nciMaxDuctStatSP nciMaxREFanCap nciMaxSupFanCap nciMinDAClSP nciMinDAHtSP nciMinDuctStatSP nciMinOAFlowSP nciMinOutTm nciMinREFanCap nciMinSupFanCap nciOAEnthSP nciOAFlowCalib nciOAInletArea nciOAMinPos nciOATSP nciRcvHrtBt nciRetFanPressSP nciSetpoints nciSpaceDehumSP nciSpaceHumSP nciTempDiff
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 12 |
Obsolete:
| no |
Key:
| 8610 |
Inheriting:
| no |
Mandatory Network Variables |
nviOccSchedule | Occupancy scheduler input.: Commands the Discharge-Air Controller into different occupancy modes typically sent by scheduler or supervisory node.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoDischAirTemp | Discharge air temperature output.: Monitors discharge-air temperature measured by a hardwired sensor.
|
Member Number:
| 35 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoUnitStatus | Unit status output.: Reports the Discharge-Air Controller status.
|
Member Number:
| 36 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
Optional Network Variables |
nviOccManCmd | Occupancy override input.: Commands the Discharge-Air Controller into different occupancy modes.
|
Member Number:
| 2 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviApplicMode | Application mode input.: Coordinates the Discharge-Air Controller with any supervisory controller.
|
Member Number:
| 3 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviEmergOverride | Emergency override input.: Commands the device into different emergency modes.
|
Member Number:
| 4 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviDuctStatPress | Duct static pressure input.: Connects a duct static pressure sensor or network output from another controller.
|
Member Number:
| 5 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0 | Maximum:
| 1250 |
|
nviDuctStaticSP | Duct static pressure setpoint input.: Sets duct static pressure setpoint of the controller via the network.
|
Member Number:
| 6 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0 | Maximum:
| 1250 |
|
nviDAClSP | Discharge air cooling setpoint input.: Sets discharge-air cooling setpoint of the controller via the network.
|
Member Number:
| 7 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,00 | Maximum:
| 30,00 |
|
nviDAHtSP | Discharge-Air heating setpoint input.: Sets discharge-air heating setpoint of the controller via the network.
|
Member Number:
| 8 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,00 | Maximum:
| 70,00 |
|
nviSupFanCap | Supply fan capacity input.: Commands override of the supply fan capacity from another controller.
|
Member Number:
| 9 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nviExhFanCap | Exhaust fan capacity input.: Connects network output from another controller to override the local exhaust fan capacity control.
|
Member Number:
| 10 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nviRetFanCap | Return fan capacity input.: Commands an override of return fan capacity from another controller.
|
Member Number:
| 11 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nviFanDiffSP | Fan differential setpoint input.: Setpoint for the percent capacity difference between the supply and return fans.
|
Member Number:
| 12 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,000 | Maximum:
| 50,000 |
|
nviBldgStatPress | Building static pressure input.: Connects network building static pressure sensor or network output from another controller.
|
Member Number:
| 13 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| -125 | Maximum:
| 125 |
|
nviBldgStaticSP | Building static pressure setpoint input.: Connects network output from another controller to provide the building static pressure setpoint.
|
Member Number:
| 14 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| -100 | Maximum:
| 100 |
|
nviPriCoolEnable | Primary cool enable input.: Connect network output from another controller to enable/disable the primary cooling output of the unit.
|
Member Number:
| 15 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviPriHeatEnable | Primary heat enable input.: Connects network output from another controller to enable/disable the primary heating outputs of the unit.
|
Member Number:
| 16 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviEconEnable | Economizer enable input.: Enables and disables economizer operation.
|
Member Number:
| 17 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviOAMinPos | Outdoor air minimum position input.: Sets minimum outdoor air damper position of controller via the network.
|
Member Number:
| 18 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nviMinOAFlowSP | Minimum outdoor airflow setpoint input.: Commands a minimum outdoor airflow rate setpoint from the network.
|
Member Number:
| 19 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0 | Maximum:
| 50000 |
|
nviOutdoorTemp | Outdoor air temperature input.: Measured outdoor air dry bulb temperature.
|
Member Number:
| 20 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| -40,00 | Maximum:
| 50,00 |
|
nviOutdoorRH | Outdoor air humidity input.: Measured outdoor air humidity in percent.
|
Member Number:
| 21 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nviOAEnthalpy | Outdoor air enthalpy input.: Connects a network outdoor air enthalpy sensor or network controller output.
|
Member Number:
| 22 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 20,00 | Maximum:
| 100,00 |
|
nviMATSP | Mixed air temperature setpoint input.: Commands a mixed air temperature setpoint from the network.
|
Member Number:
| 23 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| -10,00 | Maximum:
| 50,00 |
|
nviRATemp | Return air temperature input.: Connects a network return air temperature sensor or network output from another controller.
|
Member Number:
| 24 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| -10,00 | Maximum:
| 50,00 |
|
nviSpaceEnthalpy | Space enthalpy input.: Connects a network return air or space enthalpy sensor or network output from another controller.
|
Member Number:
| 25 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 20,00 | Maximum:
| 100,00 |
|
nviSpaceTemp | Space temperature input.: Connects a network space temperature sensor or network output from another controller.
|
Member Number:
| 26 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| -10,00 | Maximum:
| 50,00 |
|
nviSpaceRH | Space humidity input.: Connects a network return air or space relative humidity sensor or network output from another controller.
|
Member Number:
| 27 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nviHumEnable | Humidification enable input.: Enables humidification function in the controller.
|
Member Number:
| 28 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviSpaceHumSP | Space humidification setpoint input.: Connects a network space humidity setpoint or network output from another controller.
|
Member Number:
| 29 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nviDehumEnable | Dehumidification enable input.: Enables dehumidification function in the controller.
|
Member Number:
| 30 |
Base type:
| | Direction:
| input | Service:
| any |
|
nviSpaceDehumSP | Space dehumidification setpoint input.: Connects a network space dehumidification setpoint or network output from another controller.
|
Member Number:
| 31 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nviDADewPointSP | Discharge air dewpoint setpoint input.: Commands a discharge-air dewpoint setpoint from the network.
|
Member Number:
| 32 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| -20,00 | Maximum:
| 30,00 |
|
nviCWTemp | Condenser water temperature input.: Connects a network condenser water temperature sensor or network output from another controller.
|
Member Number:
| 33 |
Base type:
| | Direction:
| input | Service:
| any | Minimum:
| -10,00 | Maximum:
| 50,00 |
|
nviCWFlow | Condenser water flow input.: System condenser flow status.
|
Member Number:
| 34 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoEffDATempSP | Effective discharge-air temperature setpoint output.: Monitors the effective discharge-air temperature setpoint the Discharge-Air Controller is using for control.
|
Member Number:
| 37 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoDuctStatPress | Duct static pressure output.: Monitors the effective duct static pressure the controller is using for control.
|
Member Number:
| 38 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoEffDuctStatSP | Effective duct static pressure setpoint output.: Monitors the effective duct static pressure setpoint the Discharge-Air Controller is using for control.
|
Member Number:
| 39 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoHeatCool | Effective heat/cool output.: Actual heat/cool mode of the unit.
|
Member Number:
| 40 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoApplicMode | Application mode output.: Used to control the mode of other controllers such as a VAV box controller.
|
Member Number:
| 41 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoEffectOccup | Effective occupancy output.: Transmits the current occupancy mode of the Discharge-Air Controller for monitoring.
|
Member Number:
| 42 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoSupFanStatus | Supply fan status output.: Actual status of the supply fan for monitoring.
|
Member Number:
| 43 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoSupFanOnOff | Supply fan on/off control output.: Used to start and stop the supply fan.
|
Member Number:
| 44 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoSupFanCap | Supply fan capacity output.: Used to command the supply fan speed or capacity.
|
Member Number:
| 45 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoExhFanStatus | Exhaust fan status output.: Actual status of the exhaust fan for monitoring.
|
Member Number:
| 46 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoExhFanOnOff | Exhaust fan on/off control output.: Used to start and stop the exhaust fan.
|
Member Number:
| 47 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoExhFanCap | Exhaust fan capacity output.: Used to command the exhaust fan speed or capacity.
|
Member Number:
| 48 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoExhDamper | Exhaust damper control output.: Present status of Exhaust Damper output for monitoring or control.
|
Member Number:
| 49 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoRetFanStatus | Return fan status output.: Actual status of the return fan for monitoring.
|
Member Number:
| 50 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoRetFanOnOff | Return fan on/off control output.: Used to start and stop the return fan.
|
Member Number:
| 51 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoRetFanCap | Return fan capacity output.: Used to command the return fan speed or capacity.
|
Member Number:
| 52 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoRetFanPress | Return fan pressure output.: Present value of return fan static pressure for monitoring.
|
Member Number:
| 53 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoBldgStatPress | Building static pressure output.: Present value of the building static pressure for monitoring.
|
Member Number:
| 54 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoEconEnabled | Economizer enabled output.: Present enable/disable status of economizer for monitoring.
|
Member Number:
| 55 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoOADamper | Outdoor air damper output.: Present level of the outdoor air damper or injection fan capacity output for monitoring or control.
|
Member Number:
| 56 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoOAFlow | Outdoor airflow output.: Present value of the outdoor airflow for monitoring.
|
Member Number:
| 57 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoLocalOATemp | Local outdoor air temperature output.: Indicates value of a hardwired outdoor air temperature sensor.
|
Member Number:
| 58 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoOutdoorTemp | Outdoor air temperature output.: Present value of outdoor air temperature for monitoring.
|
Member Number:
| 59 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoLocalOARH | Local outdoor air humidity output.: Indicates value of hardwired outdoor air relative humidity sensor.
|
Member Number:
| 60 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoOutdoorRH | Outdoor air humidity output.: Present value of outdoor air humidity for monitoring.
|
Member Number:
| 61 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoOAEnthalpy | Outdoor air enthalpy output.: Present value of the outdoor air enthalpy.
|
Member Number:
| 62 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoCoolPrimary | Primary Cooling Output.: Present level of the primary cooling capacity.
|
Member Number:
| 63 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoHeatPrimary | Primary heating output.: Present value of the primary heating capacity.
|
Member Number:
| 64 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoMATemp | Mixed air temperature output.: Present value of the mixed air dry bulb temperature.
|
Member Number:
| 65 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoSpaceTemp | Space temperature output.: Present value of the space temperature for monitoring.
|
Member Number:
| 66 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoRATemp | Return air temperature output.: Present value of return air temperature for monitoring.
|
Member Number:
| 67 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoSpaceRH | Space humidity output.: Present value of the space relative humidity for monitoring.
|
Member Number:
| 68 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoSpaceEnthalpy | Space enthalpy output.: Present value of the space enthalpy.
|
Member Number:
| 69 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoEffSpaceHumSP | Effective space humidification setpoint output.: Effective space low limit humidity setpoint for monitoring.
|
Member Number:
| 70 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoHumidifier | Humidification status output.: Present level of the humidifier output for monitoring.
|
Member Number:
| 71 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoEffSpaceDHSP | Effective space dehumidification setpoint output.: Effective space high limit humidity setpoint for monitoring.
|
Member Number:
| 72 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoDehumidifier | Dehumidification status output.: Present status of dehumidification control for monitoring.
|
Member Number:
| 73 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoEffDADewPtSP | Effective discharge-air dewpoint setpoint output.: Monitors the effective discharge-air dewpoint setpoint that the discharge-air controller is using for control.
|
Member Number:
| 74 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoDADewPoint | Discharge air dewpoint temperature output.: Present value of the discharge-air dewpoint temperature.
|
Member Number:
| 75 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoCondCap | Condenser capacity output.: Present value of the condenser capacity control output for monitoring.
|
Member Number:
| 76 |
Base type:
| | Direction:
| output | Service:
| unacknowledged | Minimum:
| 0,000 | Maximum:
| 100,000 |
|
nvoLocalCWTemp | Local condenser water temperature output.: Transmits value of hardwired condenser water temperature sensor.
|
Member Number:
| 77 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoCWTemp | Condenser water temperature output.: Present value of condenser water temperature for monitoring.
|
Member Number:
| 78 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoCWFlow | Condenser water flow output.: Transmits current status of condenser water flow sensor for monitoring.
|
Member Number:
| 79 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
nvoCWPump | Condenser water pump output.: Transmits the current state of condenser water pump output for monitoring or control.
|
Member Number:
| 80 |
Base type:
| | Direction:
| output | Service:
| unacknowledged |
|
Mandatory Configuration Properties |
nciSndHrtBt | Send heartbeat.: Maximum period of time that expires before specified NV outputs will be automatically updated.
|
|
nciDAClSP | Discharge air cooling setpoint.: Default discharge-air cooling setpoint for the Discharge-Air Controller.
|
|
nciDAHtSP | Discharge air heating setpoint.: Default discharge-air heating setpoint for the Discharge-Air Controller.
|
|
Optional Configuration Properties |
nciSetpoints | Occupancy temperature setpoints.: Space temperature setpoints for various heat, cool and occupancy modes.
|
|
nciMinOutTm | Minimum send time.: Minimum time between automatic NV output transmissions.
|
|
nciRcvHrtBt | Receive heartbeat.: Controls maximum time after last update before default values are used.
|
|
nciLocation | Location label.: Provides descriptive physical location information related to the object.
|
|
nciBypassTime | Local bypass time.: Maximum time the controller can be in bypass mode following request.
|
|
nciMaxSupFanCap | Maximum supply fan capacity.: Maximum supply fan capacity setpoint for the Discharge-Air Controller.
|
|
nciMinSupFanCap | Minimum supply fan capacity.: Minimum supply fan capacity setpoint for the Discharge-Air Controller.
|
|
nciMaxREFanCap | Maximum return/exhaust fan capacity.: Maximum return/exhaust fan capacity setpoint for the Discharge-Air Controller.
|
|
nciMinREFanCap | Minimum return/exhaust fan capacity.: Minimum return/exhaust fan capacity setpoint for the Discharge-Air Controller.
|
|
nciDuctStatSP | Duct static pressure setpoint.: Default duct static pressure setpoint for the Discharge-Air Controller.
|
|
nciMaxDuctStatSP | Maximum duct static pressure setpoint.: Maximum duct static pressure setpoint for the Discharge-Air Controller.
|
|
nciMinDuctStatSP | Minimum duct static pressure setpoint.: Minimum duct static pressure setpoint for the Discharge-Air Controller.
|
|
nciDuctStatLim | Duct static pressure limit.: Duct static pressure limit, used for equipment protection.
|
|
nciBldgStaticSP | Building static pressure setpoint.: Default building static pressure setpoint for the Discharge-Air Controller.
|
|
nciRetFanPressSP | Return fan pressure setpoint.: Return fan static pressure setpoint for the Discharge-Air Controller.
|
|
nciFanDiffSP | Fan differential setpoint.: Default for percent capacity difference between supply and return fans.
|
|
nciMALowLimitSP | Mixed air low limit setpoint.: Mixed air low limit setpoint for the Discharge-Air Controller.
|
|
nciMATSP | Mixed air temperature setpoint.: Default mixed air temperature setpoint for the Discharge-Air Controller.
|
|
nciOAMinPos | Outdoor air damper minimum position.: Default minimum outdoor air damper position setpoint for the Discharge-Air Controller.
|
Member Number:
| 22 |
Base type:
| |
Applies to
| nvoOADamper | Array:
| not permitted |
|
nciMinOAFlowSP | Minimum outdoor airflow setpoint.: Default minimum outdoor airflow setpoint for the Discharge-Air Controller.
|
|
nciOAFlowCalib | Outdoor airflow calibration.: Gain for the outdoor airflow calibration for the Discharge-Air Controller.
|
|
nciOAInletArea | Outdoor air inlet area.: Area of the outdoor air inlet for the Discharge-Air Controller.
|
|
nciOATSP | Outdoor air temperature setpoint.: Airside economizer outdoor air temperature enable setpoint for the Discharge-Air Controller.
|
|
nciOAEnthSP | Outdoor air enthalpy setpoint.: Default airside economizer outdoor air enthalpy enable setpoint for the Discharge-Air Controller.
|
|
nciTempDiff | Economizer enable differential temperature setpoint.: Differential between entering air temp and entering condenser water temp to enable economizer operation.
|
|
nciExhStartPos | Exhaust enable position.: Exhaust enable outdoor air damper position setpoint for the Discharge-Air Controller.
|
|
nciSpaceHumSP | Space humidification setpoint.: Default space humidification setpoint for the Discharge-Air Controller.
|
|
nciSpaceDehumSP | Space dehumidification setpoint.: Default space dehumidification setpoint for the Discharge-Air Controller.
|
|
nciDADewPointSP | Discharge air dewpoint setpoint.: Default discharge-air dewpoint setpoint for the Discharge-Air Controller.
|
|
nciMaxDAClSP | Maximum discharge air cooling setpoint.: Maximum discharge-air cooling setpoint for the Discharge-Air Controller.
|
|
nciMinDAClSP | Minimum discharge air cooling setpoint.: Minimum discharge-air cooling setpoint for the Discharge-Air Controller.
|
|
nciMaxDAHtSP | Maximum discharge air heating setpoint.: Maximum discharge heating setpoint for the Discharge-Air Controller.
|
|
nciMinDAHtSP | Minimum discharge air heating setpoint.: Minimum discharge heating setpoint for the Discharge-Air Controller.
|
|
nciCoolLockout | Cooling lockout temperature setpoint.: Outdoor air temperature cooling lockout setpoint for the Discharge-Air Controller.
|
|
nciHeatLockout | Heating lockout temperature setpoint.: Outdoor air temperature heating lockout setpoint for the Discharge-Air Controller.
|
|
nciCoolResetEn | Cooling reset enable.: Enables/disables the discharge-air temperature cooling reset control for the Discharge-Air Controller.
|
|
nciHeatResetEn | Heating reset enable.: Enables/disables the discharge-air temperature heating reset control for the Discharge-Air Controller.
|
|